title: "NEXTRACKER LLC: NXPCS1670K-HUD Inverter (1,673,400W)"
url: https://epri-peac.com/solar-equipment/inverters/nextracker-llc/nextracker-llc-nxpcs1670k-hud-800v/
description: "CEC specs for NEXTRACKER LLC: NXPCS1670K-HUD {800V}: 1,673,400W AC, 800V, 1550A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# NEXTRACKER LLC: NXPCS1670K-HUD {800V} — CEC Inverter Specifications

Manufacturer: [**NEXTRACKER LLC**](https://epri-peac.com/solar-equipment/brands/nextracker-llc/) Registry: **CEC Verified Engineering Specification**

NEXTRACKER LLC: NXPCS1670K-HUD {800V} outputs 1,673,400 W AC at 800 V, 3-phase (1207.7 A continuous, 1,550 A OCPD), ranking #290 of 2,343 CEC inverters at 98.11% efficiency with a 1,200-1,500 V MPPT window and 1,500 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 1,673,400 W

- **AC Voltage** : 800 V, 3-phase

- **Min PV Breaker** : 1,550 A (parallel Cu feeders)

- **CEC Efficiency** : 98.11%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does NEXTRACKER LLC: NXPCS1670K-HUD {800V} Compare Against Peer CEC Listings?

Breaker sizing (1,550 A), parallel Cu feeders wire rules, and DC input limits for NEXTRACKER LLC: NXPCS1670K-HUD {800V}.

For NEC 705.12 solar interconnection, NEXTRACKER LLC: NXPCS1670K-HUD {800V} outputs 1207.7 A continuous AC at 800 V, 3-phase and needs a 1,550 A backfeed breaker on parallel Cu feeders (75 C). Commercial 800 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (800V) or NEC 705.11 supply-side tap. Conversion efficiency scores 98.11% (#290 of 2,343, +1.29 pts vs overall CEC median).

## Where Does NEXTRACKER LLC: NXPCS1670K-HUD {800V} Fall Across Listed CEC Models?

Output power comparison showing where NEXTRACKER LLC: NXPCS1670K-HUD {800V} sits among all 2,343 CEC-listed grid-support inverters. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

## What Dataset Percentiles Define NEXTRACKER LLC: NXPCS1670K-HUD {800V}?

Relative ranking of NEXTRACKER LLC: NXPCS1670K-HUD {800V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.

## What Do the Dataset Ranks Show for NEXTRACKER LLC: NXPCS1670K-HUD {800V}?

Snapshot of NEXTRACKER LLC: NXPCS1670K-HUD {800V} efficiency rank (#290), OCPD breaker size, MPPT span, and busbar verdict. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

Eff #290 / 2,343

### 98.11% CEC Weighted Efficiency

-0.19 pts vs the 98.3% 800 V median; overall power rank #119 (1,673,400 W, top 5.1%; higher than 94.9% of peers).

NEC 705.12 Check

### 1,550 A Required Backfeed OCPD

125% x 1207.7 A = 1509.6 A -> 1,550 A standard OCPD using parallel Cu feeders (75 C).

MPPT Window

### 1,200 V - 1,500 V (Max 1,500 V DC)

Tracking span of 300.0 V; active in CEC directory (hybrid battery-capable inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 800 V, 3-phase switchgear (200A Bus / 200A Main (800V) to 1,200A Bus / 1,200A Main (800V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 1673400.0W / 800 V 3-phase -> 1207.7 A | Breaker >= 1.25 * 1207.7 = 1509.6 A -> 1,550 A

CEC Inverters.csv for NEXTRACKER LLC: NXPCS1670K-HUD {800V}: Paco=1673400.0 W, Vac=800 V, Vdcmax=1500.0 V, Eff=98.11%.

**Result:** Min 1,550 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (800V): Supply-Side Tap (705.11) / Dedicated Switchboard.

## What Are the Published CEC Specifications for NEXTRACKER LLC: NXPCS1670K-HUD {800V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for NEXTRACKER LLC: NXPCS1670K-HUD {800V}. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.

Official California Energy Commission (NREL SAM) test parameters for NEXTRACKER LLC: NXPCS1670K-HUD {800V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 1,673,400 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 800 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 1,500 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 1,200 V - 1,500 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 1263.45 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 98.11% | Calculated AC/DC conversion ratio from CEC test protocol |
| **Inverter Topology** | Hybrid: Yes (Battery Capable) | CEC Solar Equipment List grid-support certification |

## What Switchgear Limits Apply to NEXTRACKER LLC: NXPCS1670K-HUD {800V} (800 V, 3-phase)?

NEC 705.12(B)(3)(2) backfeed compliance table for NEXTRACKER LLC: NXPCS1670K-HUD {800V} at 800 V, 3-phase. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Evaluates NEXTRACKER LLC: NXPCS1670K-HUD {800V} (1550 A required OCPD at 800 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (800V)** | 40 A | 1,550 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (800V)** | 80 A | 1,550 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (800V)** | 120 A | 1,550 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (800V)** | 160 A | 1,550 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (800V)** | 240 A | 1,550 A | Supply-Side Tap (705.11) / Dedicated Switchboard |

## Which Competing Grid-Support Inverters Compare to NEXTRACKER LLC: NXPCS1670K-HUD {800V}?

Peer 800 V, 3-phase CEC inverters near 1,673,400 W AC output such as Sungrow Power Supply Co Ltd: SC2000UD-US {800V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Sungrow Power Supply Co Ltd: SC2000UD-US {800V}**](https://epri-peac.com/solar-equipment/inverters/sungrow-power-supply-co-ltd/sungrow-power-supply-co-ltd-sc2000ud-us-800v/) Sungrow Power Supply Co Ltd | 2,014,870 W | +341470 W | 800.0 V | 1500.0 V | 97.8% |
| [**DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {800V}**](https://epri-peac.com/solar-equipment/inverters/dynapower-company-llc/dynapower-company-llc-cps-1250-gen5-800v/) DYNAPOWER COMPANY LLC | 1,294,180 W | -379220 W | 800.0 V | 1500.0 V | 98.82% |
| [**Sichuan Clou Energy Electric Co Ltd: NEPCS-2300 {800V}**](https://epri-peac.com/solar-equipment/inverters/sichuan-clou-energy-electric-co-ltd/sichuan-clou-energy-electric-co-ltd-nepcs-2300-800v/) Sichuan Clou Energy Electric Co Ltd | 2,299,960 W | +626560 W | 800.0 V | 1500.0 V | 98.5% |
| [**Delta Electronics: DP350U-US-XX {800V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-dp350u-us-xx-800v/) Delta Electronics | 352,401 W | -1320999 W | 800.0 V | 1330.0 V | 98.48% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for NEXTRACKER LLC: NXPCS1670K-HUD {800V}?

Check NEXTRACKER LLC: NXPCS1670K-HUD {800V} (1,673,400 W AC, 1,550 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 800 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (800V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,500 V DC on NEXTRACKER LLC: NXPCS1670K-HUD {800V}.

### NEXTRACKER LLC: NXPCS1670K-HUD {800V} Panel & Wire Spec

Size 75 C copper conductors at parallel Cu feeders on a 1,550 A OCPD breaker (1207.7 A continuous).

### Alternative Inverter Comparison

Compare efficiency (98.11%) and MPPT window (1,200-1,500 V) directly against Sungrow Power Supply Co Ltd: SC2000UD-US {800V} (2,014,870 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for NEXTRACKER LLC: NXPCS1670K-HUD {800V} by NEXTRACKER LLC covering breaker sizing, MPPT limits, and 800 V, 3-phase interconnection.

### What breaker and wire size does NEXTRACKER LLC: NXPCS1670K-HUD {800V} require?

At 1,673,400 W continuous AC (800 V, 3-phase), continuous current is 1207.7 A; 125% NEC 690.8/705.12 sizing requires a 1,550 A breaker and parallel Cu feeders (75 C) wire.

### What commercial switchgear or feeder sizing does NEXTRACKER LLC: NXPCS1670K-HUD {800V} require?

At 1,673,400 W AC and 800 V, 3-phase, continuous line current is 1207.7 A, requiring a 1,550 A OCPD and 1,200A Bus / 1,200A Main (800V) or NEC 705.11 interconnection.

### How does NEXTRACKER LLC: NXPCS1670K-HUD {800V} compare to Sungrow Power Supply Co Ltd: SC2000UD-US {800V}?

NEXTRACKER LLC: NXPCS1670K-HUD {800V} delivers 1,673,400 W AC at 98.11% CEC efficiency with a 1,500 V DC ceiling, while Sungrow Power Supply Co Ltd: SC2000UD-US {800V} outputs 2,014,870 W at 800 V, 3-phase.

## Related Pages

Explore NEXTRACKER LLC hardware, Sungrow Power Supply Co Ltd: SC2000UD-US {800V}, utility rates, and NEC 705.12 sizing calculators alongside NEXTRACKER LLC: NXPCS1670K-HUD {800V}.

[All NEXTRACKER LLC Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/nextracker-llc/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From NEXTRACKER LLC

- [All NEXTRACKER LLC Specs](https://epri-peac.com/solar-equipment/brands/nextracker-llc/)
- [NEXTRACKER LLC: NXPCS5000K-HUD {800V}](https://epri-peac.com/solar-equipment/inverters/nextracker-llc/nextracker-llc-nxpcs5000k-hud-800v/)
- [NEXTRACKER LLC: NXPCS3340K-HUD {800V}](https://epri-peac.com/solar-equipment/inverters/nextracker-llc/nextracker-llc-nxpcs3340k-hud-800v/)
- [NEXTRACKER LLC: NXPCS800K-HUD {800V}](https://epri-peac.com/solar-equipment/inverters/nextracker-llc/nextracker-llc-nxpcs800k-hud-800v/)