Manufacturer: [**LS Energy Solutions LLC**](https://epri-peac.com/solar-equipment/brands/ls-energy-solutions-llc/) Registry: **CEC Verified Engineering Specification**

LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V} outputs 140,485 W AC at 480 V, 3-phase (169.0 A continuous, 225 A OCPD), ranking #355 of 2,343 CEC inverters at 97.98% efficiency with a 720-1,150 V MPPT window and 1,150 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 140,485 W

- **AC Voltage** : 480 V, 3-phase

- **Min PV Breaker** : 225 A (4/0 AWG Cu)

- **CEC Efficiency** : 97.98%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V} Compare Against Peer CEC Listings?

NEC 705.12 breaker requirements, efficiency placement, and 480 V, 3-phase grid-support overview for LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V}.

Ranking #278 of 2,343 CEC inverters (top 11.9%; higher than 88.1% of peers), LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V} is a grid-tied PV inverter delivering 140,485 W continuous AC at 480 V, 3-phase (169.0 A continuous). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap. Weighted CEC efficiency reaches 97.98% (-0.04 pts vs the 98.02% 480 V median) against peers like Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V} (125,000 W).

## Where Does LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V} Fall Across Listed CEC Models?

Marks LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V} (140,485 W AC) across the California Energy Commission inverter AC capacity distribution.

## What Dataset Percentiles Define LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V}?

Benchmarks LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V} continuous AC output, 97.98% CEC weighted efficiency, and 225 A OCPD breaker demand.

## What Do the Dataset Ranks Show for LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V}?

Four key NEC 705.12 and California Energy Commission metrics defining LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V} by LS Energy Solutions LLC.

Eff #355 / 2,343

### 97.98% CEC Weighted Efficiency

-0.04 pts vs the 98.02% 480 V median; overall power rank #278 (140,485 W, top 11.9%; higher than 88.1% of peers).

NEC 705.12 Check

### 225 A Required Backfeed OCPD

125% x 169.0 A = 211.2 A -> 225 A standard OCPD using 4/0 AWG Cu (75 C).

MPPT Window

### 720 V - 1,150 V (Max 1,150 V DC)

Tracking span of 430.0 V; listed since 2021-08-02 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 140485.0W / 480 V 3-phase -> 169.0 A | Breaker >= 1.25 * 169.0 = 211.2 A -> 225 A

CEC Inverters.csv for LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V}: Paco=140485.0 W, Vac=480 V, Vdcmax=1150.0 V, Eff=97.98%.

**Result:** Min 225 A breaker & 4/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V}?

Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V}.

Official California Energy Commission (NREL SAM) test parameters for LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 140,485 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 1,150 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 720 V - 1,150 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 153.342 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 97.98% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2021-08-02 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V} (480 V, 3-phase)?

Evaluates LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V} (225 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.

Evaluates LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V} (225 A required OCPD at 480 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (480V)** | 40 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (480V)** | 80 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (480V)** | 120 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (480V)** | 160 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (480V)** | 240 A | 225 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V}?

Sample PV string lengths aligned within 720-1,150 V MPPT and 1,150 V DC max at -10 C. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

Sampled CEC PV modules aligned within 720.0-1150.0 V MPPT and 1150.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 17 to 20 panels | 11.8 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 22 to 27 panels | 11.88 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 21 to 25 panels | 10.62 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 25 to 28 panels | 5.6 kW |

## Which Competing Grid-Support Inverters Compare to LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V}?

Competing CEC grid-support inverters near 140,485 W AC and 480 V, 3-phase, led by Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V}**](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-ecb125ktl-m-us-480-480v/) Chint Power Systems America | 125,000 W | -15485 W | 480.0 V | 1100.0 V | 97.2% |
| [**Delta Electronics: DES10JB125K01 {480V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-des10jb125k01-480v/) Delta Electronics | 125,000 W | -15485 W | 480.0 V | 1000.0 V | 97.01% |
| [**Delta Electronics: PCS125 {480V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-pcs125-480v/) Delta Electronics | 125,000 W | -15485 W | 480.0 V | 1000.0 V | 97.01% |
| [**Ginlong Technologies Co Ltd: S5-GC125K-US {480V}**](https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-s5-gc125k-us-480v/) Ginlong Technologies Co Ltd | 124,991 W | -15494 W | 480.0 V | 850.0 V | 97.88% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V}?

Check LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V} (140,485 W AC, 225 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,150 V DC on LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V}.

### LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V} Panel & Wire Spec

Size 75 C copper conductors at 4/0 AWG Cu on a 225 A OCPD breaker (169.0 A continuous).

### Alternative Inverter Comparison

Compare efficiency (97.98%) and MPPT window (720-1,150 V) directly against Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V} (125,000 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V} by LS Energy Solutions LLC covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.

### What breaker and wire size does LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V} require?

At 140,485 W continuous AC (480 V, 3-phase), continuous current is 169.0 A; 125% NEC 690.8/705.12 sizing requires a 225 A breaker and 4/0 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V} require?

At 140,485 W AC and 480 V, 3-phase, continuous line current is 169.0 A, requiring a 225 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

### How does LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V} compare to Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V}?

LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V} delivers 140,485 W AC at 97.98% CEC efficiency with a 1,150 V DC ceiling, while Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V} outputs 125,000 W at 480 V, 3-phase.

## Related Pages

Explore LS Energy Solutions LLC hardware, Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V}, utility rates, and NEC 705.12 sizing calculators alongside LS Energy Solutions LLC: PBE-5140-R61-1A0-1000 {480V}.

[All LS Energy Solutions LLC Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/ls-energy-solutions-llc/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From LS Energy Solutions LLC

- [All LS Energy Solutions LLC Specs](https://epri-peac.com/solar-equipment/brands/ls-energy-solutions-llc/)
- [LS Energy Solutions LLC: PBE-6140-R61-1A0-1000 {600V}](https://epri-peac.com/solar-equipment/inverters/ls-energy-solutions-llc/ls-energy-solutions-llc-pbe-6140-r61-1a0-1000-600v/)