title: "JingTsing Technology Ltd Inverter (459,563W)"
url: https://epri-peac.com/solar-equipment/inverters/jingtsing-technology-ltd/jingtsing-technology-ltd-jtes-pcs450k-1600-740-l03c1-740v/
description: "CEC specs for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}: 459,563W AC, 740V, 450A OCPD, and NEC 705.12 checks."
---

CEC Grid-Support Inverter

# JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} — CEC Inverter Specifications

Manufacturer: [**JingTsing Technology Ltd**](https://epri-peac.com/solar-equipment/brands/jingtsing-technology-ltd/) Registry: **CEC Verified Engineering Specification**

JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} outputs 459,563 W AC at 740 V, 3-phase (358.6 A continuous, 450 A OCPD), ranking #81 of 2,343 CEC inverters at 98.48% efficiency with a 1,100-1,600 V MPPT window and 1,600 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 459,563 W

- **AC Voltage** : 740 V, 3-phase

- **Min PV Breaker** : 450 A (parallel Cu feeders)

- **CEC Efficiency** : 98.48%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} Compare Against Peer CEC Listings?

CEC efficiency rank (#81), 1,100-1,600 V MPPT tracking, and panel fit for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}.

Operating at 740 V, 3-phase, JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} converts DC array energy at 98.48% CEC weighted efficiency (top 3.6%; higher than 96.4% of peers) with a 1,600 V max DC input and 333.323 A max input current for NEC 690.7 string safety. Compare this 459,563 W grid-tied PV inverter directly with EPC Power Corp: 50-200100 {720V} (561,806 W). Commercial 740 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (740V) or NEC 705.11 supply-side tap.

## Where Does JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} Fall Across Listed CEC Models?

CEC inverter wattage histogram highlighting JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} at 459,563 W continuous AC output. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

## What Dataset Percentiles Define JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}?

Dataset percentiles comparing JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} against 2,343 certified grid-support inverters nationwide. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.

## What Do the Dataset Ranks Show for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}?

Engineering highlights for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} covering efficiency, parallel Cu feeders feeder, and panel compatibility.

Eff #81 / 2,343

### 98.48% CEC Weighted Efficiency

equal to the 98.48% 740 V median; overall power rank #205 (459,563 W, top 8.7%; higher than 91.3% of peers).

NEC 705.12 Check

### 450 A Required Backfeed OCPD

125% x 358.6 A = 448.2 A -> 450 A standard OCPD using parallel Cu feeders (75 C).

MPPT Window

### 1,100 V - 1,600 V (Max 1,600 V DC)

Tracking span of 500.0 V; active in CEC directory (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 740 V, 3-phase switchgear (200A Bus / 200A Main (740V) to 1,200A Bus / 1,200A Main (740V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 459563.0W / 740 V 3-phase -> 358.6 A | Breaker >= 1.25 * 358.6 = 448.2 A -> 450 A

CEC Inverters.csv for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}: Paco=459563.0 W, Vac=740 V, Vdcmax=1600.0 V, Eff=98.48%.

**Result:** Min 450 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (740V): Supply-Side Tap (705.11) / Dedicated Switchboard.

## What Are the Published CEC Specifications for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}?

California Energy Commission Solar Equipment List parameters for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} (grid-tied PV inverter) interconnection.

Official California Energy Commission (NREL SAM) test parameters for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 459,563 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 740 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 1,600 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 1,100 V - 1,600 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 333.323 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 98.48% | Calculated AC/DC conversion ratio from CEC test protocol |
| **Inverter Topology** | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |

## What Switchgear Limits Apply to JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} (740 V, 3-phase)?

Panelboard and switchgear backfeed allowances for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} (450 A OCPD). Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

Evaluates JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} (450 A required OCPD at 740 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (740V)** | 40 A | 450 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (740V)** | 80 A | 450 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (740V)** | 120 A | 450 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (740V)** | 160 A | 450 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (740V)** | 240 A | 450 A | Supply-Side Tap (705.11) / Dedicated Switchboard |

## Which CEC PV Module Strings Pair With JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}?

Representative PV panel pairings verified under NEC 690.7 cold Voc for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.

Sampled CEC PV modules aligned within 1100.0-1600.0 V MPPT and 1600.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 26 to 28 panels | 16.52 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 33 to 37 panels | 16.28 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 32 to 35 panels | 14.88 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 39 panels (fixed) | 7.8 kW |

## Which Competing Grid-Support Inverters Compare to JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}?

Four alternative CEC inverters matched to JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} (459,563 W AC), led by EPC Power Corp: 50-200100 {720V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**EPC Power Corp: 50-200100 {720V}**](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-200100-720v/) EPC Power Corp | 561,806 W | +102243 W | 720.0 V | 1500.0 V | 98.58% |
| [**ABB: PVS-175-TL-POWER-MODULE-1-US {800V}**](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-175-tl-power-module-1-us-800v/) ABB | 179,574 W | -279989 W | 800.0 V | 1200.0 V | 97.39% |
| [**LS Energy Solutions LLC: PBE-6140-R61-1A0-1000 {600V}**](https://epri-peac.com/solar-equipment/inverters/ls-energy-solutions-llc/ls-energy-solutions-llc-pbe-6140-r61-1a0-1000-600v/) LS Energy Solutions LLC | 139,449 W | -320114 W | 600.0 V | 1350.0 V | 98.27% |
| [**SMA America: SHP FLEX-US-21 {385V}**](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-shp-flex-us-21-385v/) SMA America | 100,842 W | -358721 W | 385.0 V | 1195.0 V | 97.8% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}?

Check JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} (459,563 W AC, 450 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 740 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (740V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,600 V DC on JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}.

### JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} Panel & Wire Spec

Size 75 C copper conductors at parallel Cu feeders on a 450 A OCPD breaker (358.6 A continuous).

### Alternative Inverter Comparison

Compare efficiency (98.48%) and MPPT window (1,100-1,600 V) directly against EPC Power Corp: 50-200100 {720V} (561,806 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} by JingTsing Technology Ltd covering breaker sizing, MPPT limits, and 740 V, 3-phase interconnection.

### What breaker and wire size does JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} require?

At 459,563 W continuous AC (740 V, 3-phase), continuous current is 358.6 A; 125% NEC 690.8/705.12 sizing requires a 450 A breaker and parallel Cu feeders (75 C) wire.

### What commercial switchgear or feeder sizing does JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} require?

At 459,563 W AC and 740 V, 3-phase, continuous line current is 358.6 A, requiring a 450 A OCPD and 1,200A Bus / 1,200A Main (740V) or NEC 705.11 interconnection.

### How does JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} compare to EPC Power Corp: 50-200100 {720V}?

JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} delivers 459,563 W AC at 98.48% CEC efficiency with a 1,600 V DC ceiling, while EPC Power Corp: 50-200100 {720V} outputs 561,806 W at 740 V, 3-phase.

## Related Pages

Explore JingTsing Technology Ltd hardware, EPC Power Corp: 50-200100 {720V}, utility rates, and NEC 705.12 sizing calculators alongside JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}.

[All JingTsing Technology Ltd Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/jingtsing-technology-ltd/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From JingTsing Technology Ltd

- [All JingTsing Technology Ltd Specs](https://epri-peac.com/solar-equipment/brands/jingtsing-technology-ltd/)
- [JingTsing Technology Ltd: JTES-PCS125K-1000/480-L03C1 {480V}](https://epri-peac.com/solar-equipment/inverters/jingtsing-technology-ltd/jingtsing-technology-ltd-jtes-pcs125k-1000-480-l03c1-480v/)
- [JingTsing Technology Ltd: JTES-PCS125K-1000/480-L03L1 {480V}](https://epri-peac.com/solar-equipment/inverters/jingtsing-technology-ltd/jingtsing-technology-ltd-jtes-pcs125k-1000-480-l03l1-480v/)