title: "INGETEAM POWER TECHNOLOGY SA Inverter (1,042,220W)"
url: https://epri-peac.com/solar-equipment/inverters/ingeteam-power-technology-sa/ingeteam-power-technology-sa-ingecon-sun-1245tl-u-b480-480v/
description: "CEC specs for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}: 1,042,220W AC, 480V, 1600A OCPD, and NEC 705.12 checks."
---

CEC Grid-Support Inverter

# INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} — CEC Inverter Specifications

Manufacturer: [**INGETEAM POWER TECHNOLOGY SA**](https://epri-peac.com/solar-equipment/brands/ingeteam-power-technology-sa/) Registry: **CEC Verified Engineering Specification**

INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} outputs 1,042,220 W AC at 480 V, 3-phase (1253.6 A continuous, 1,600 A OCPD), ranking #1,149 of 2,343 CEC inverters at 96.84% efficiency with a 697-1,200 V MPPT window and 1,200 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 1,042,220 W

- **AC Voltage** : 480 V, 3-phase

- **Min PV Breaker** : 1,600 A (parallel Cu feeders)

- **CEC Efficiency** : 96.84%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} Compare Against Peer CEC Listings?

Breaker sizing (1,600 A), parallel Cu feeders wire rules, and DC input limits for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}.

Classified as a hybrid battery-capable inverter (active in CEC directory), INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} requires 1567.0 A design capacity -> 1,600 A breaker using parallel Cu feeders copper at 75 C terminals. Weighted efficiency sits at 96.84% (+0.02 pts vs overall CEC median) across 2,343 CEC models, while commercial 480 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (480v) or nec 705.11 supply-side tap.

## Where Does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} Fall Across Listed CEC Models?

Output power comparison showing where INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} sits among all 2,343 CEC-listed grid-support inverters.

## What Dataset Percentiles Define INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}?

Relative ranking of INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.

## What Do the Dataset Ranks Show for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}?

Snapshot of INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} efficiency rank (#1,149), OCPD breaker size, MPPT span, and busbar verdict.

Eff #1,149 / 2,343

### 96.84% CEC Weighted Efficiency

-1.18 pts vs the 98.02% 480 V median; overall power rank #163 (1,042,220 W, top 7.0%; higher than 93.0% of peers).

NEC 705.12 Check

### 1,600 A Required Backfeed OCPD

125% x 1253.6 A = 1567.0 A -> 1,600 A standard OCPD using parallel Cu feeders (75 C).

MPPT Window

### 697 V - 1,200 V (Max 1,200 V DC)

Tracking span of 503.0 V; active in CEC directory (hybrid battery-capable inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 1042220.0W / 480 V 3-phase -> 1253.6 A | Breaker >= 1.25 * 1253.6 = 1567.0 A -> 1,600 A

CEC Inverters.csv for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}: Paco=1042220.0 W, Vac=480 V, Vdcmax=1200.0 V, Eff=96.84%.

**Result:** Min 1,600 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (480V): Supply-Side Tap (705.11) / Dedicated Switchboard.

## What Are the Published CEC Specifications for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}.

Official California Energy Commission (NREL SAM) test parameters for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 1,042,220 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 1,200 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 697 V - 1,200 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 1134.09 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 96.84% | Calculated AC/DC conversion ratio from CEC test protocol |
| **Inverter Topology** | Hybrid: Yes (Battery Capable) | CEC Solar Equipment List grid-support certification |

## What Switchgear Limits Apply to INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} (480 V, 3-phase)?

NEC 705.12(B)(3)(2) backfeed compliance table for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} at 480 V, 3-phase.

Evaluates INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} (1600 A required OCPD at 480 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (480V)** | 40 A | 1,600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (480V)** | 80 A | 1,600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (480V)** | 120 A | 1,600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (480V)** | 160 A | 1,600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (480V)** | 240 A | 1,600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |

## Which CEC PV Module Strings Pair With INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}?

Minimum and maximum series solar module strings fitting INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} MPPT and 1,200 V limits.

Sampled CEC PV modules aligned within 697.0-1200.0 V MPPT and 1200.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 17 to 21 panels | 12.39 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 21 to 28 panels | 12.32 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 21 to 26 panels | 11.05 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 25 to 29 panels | 5.8 kW |

## Which Competing Grid-Support Inverters Compare to INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}?

Peer 480 V, 3-phase CEC inverters near 1,042,220 W AC output such as EPC Power Corp: 50-100181 {480V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**EPC Power Corp: 50-100181 {480V}**](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100181-480v/) EPC Power Corp | 1,044,200 W | +1980 W | 480.0 V | 1500.0 V | 97.49% |
| [**EPC Power Corp: 50-100100 {480V}**](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100100-480v/) EPC Power Corp | 1,036,840 W | -5380 W | 480.0 V | 1250.0 V | 95.42% |
| [**DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V}**](https://epri-peac.com/solar-equipment/inverters/dynapower-company-llc/dynapower-company-llc-cps-1500-gen4-480v/) DYNAPOWER COMPANY LLC | 1,199,640 W | +157420 W | 480.0 V | 1500.0 V | 96.13% |
| [**Delta Electronics: EPCS-1200US {480V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-epcs-1200us-480v/) Delta Electronics | 1,216,710 W | +174490 W | 480.0 V | 1500.0 V | 97.82% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}?

Check INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} (1,042,220 W AC, 1,600 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,200 V DC on INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}.

### INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} Panel & Wire Spec

Size 75 C copper conductors at parallel Cu feeders on a 1,600 A OCPD breaker (1253.6 A continuous).

### Alternative Inverter Comparison

Compare efficiency (96.84%) and MPPT window (697-1,200 V) directly against EPC Power Corp: 50-100181 {480V} (1,044,200 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} by INGETEAM POWER TECHNOLOGY SA covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.

### What breaker and wire size does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} require?

At 1,042,220 W continuous AC (480 V, 3-phase), continuous current is 1253.6 A; 125% NEC 690.8/705.12 sizing requires a 1,600 A breaker and parallel Cu feeders (75 C) wire.

### What commercial switchgear or feeder sizing does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} require?

At 1,042,220 W AC and 480 V, 3-phase, continuous line current is 1253.6 A, requiring a 1,600 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

### How does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} compare to EPC Power Corp: 50-100181 {480V}?

INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} delivers 1,042,220 W AC at 96.84% CEC efficiency with a 1,200 V DC ceiling, while EPC Power Corp: 50-100181 {480V} outputs 1,044,200 W at 480 V, 3-phase.

## Related Pages

Explore INGETEAM POWER TECHNOLOGY SA hardware, EPC Power Corp: 50-100181 {480V}, utility rates, and NEC 705.12 sizing calculators alongside INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}.

[All INGETEAM POWER TECHNOLOGY SA Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/ingeteam-power-technology-sa/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From INGETEAM POWER TECHNOLOGY SA

- [All INGETEAM POWER TECHNOLOGY SA Specs](https://epri-peac.com/solar-equipment/brands/ingeteam-power-technology-sa/)
- [INGETEAM POWER TECHNOLOGY SA: INGECON SUN 3825TL U C690 {690V}](https://epri-peac.com/solar-equipment/inverters/ingeteam-power-technology-sa/ingeteam-power-technology-sa-ingecon-sun-3825tl-u-c690-690v/)
- [INGETEAM POWER TECHNOLOGY SA: INGECON SUN STORAGE 3660TL U C690 {690V}](https://epri-peac.com/solar-equipment/inverters/ingeteam-power-technology-sa/ingeteam-power-technology-sa-ingecon-sun-storage-3660tl-u-c690-690v/)
- [INGETEAM POWER TECHNOLOGY SA: INGECON SUN 3825TL U C675 {675V}](https://epri-peac.com/solar-equipment/inverters/ingeteam-power-technology-sa/ingeteam-power-technology-sa-ingecon-sun-3825tl-u-c675-675v/)
- [INGETEAM POWER TECHNOLOGY SA: INGECON SUN 3825TL U C660 {660V}](https://epri-peac.com/solar-equipment/inverters/ingeteam-power-technology-sa/ingeteam-power-technology-sa-ingecon-sun-3825tl-u-c660-660v/)
- [INGETEAM POWER TECHNOLOGY SA: INGECON SUN STORAGE 3660TL U C660 {660V}](https://epri-peac.com/solar-equipment/inverters/ingeteam-power-technology-sa/ingeteam-power-technology-sa-ingecon-sun-storage-3660tl-u-c660-660v/)