title: "GoodWe Technologies Co Ltd Inverter (8,301W)"
url: https://epri-peac.com/solar-equipment/inverters/goodwe-technologies-co-ltd/goodwe-technologies-co-ltd-gep96-1-us30-208v/
description: "CEC specs for GoodWe Technologies Co Ltd: GEP96-1-US30 {208V}: 8,301W AC, 208V, 50A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# GoodWe Technologies Co Ltd: GEP96-1-US30 {208V} — CEC Inverter Specifications

Manufacturer: [**GoodWe Technologies Co Ltd**](https://epri-peac.com/solar-equipment/brands/goodwe-technologies-co-ltd/) Registry: **CEC Verified Engineering Specification**

GoodWe Technologies Co Ltd: GEP96-1-US30 {208V} outputs 8,301 W AC at 208 V, commercial single-phase (39.9 A continuous, 50 A OCPD), ranking #1,938 of 2,343 CEC inverters at 96.03% efficiency with a 182-500 V MPPT window and 500 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 8,301 W

- **AC Voltage** : 208 V, commercial single-phase

- **Min PV Breaker** : 50 A (8 AWG Cu)

- **CEC Efficiency** : 96.03%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does GoodWe Technologies Co Ltd: GEP96-1-US30 {208V} Compare Against Peer CEC Listings?

How GoodWe Technologies Co Ltd GoodWe Technologies Co Ltd: GEP96-1-US30 {208V} compares on 96.03% efficiency, MPPT span, and 120% busbar interconnection.

GoodWe Technologies Co Ltd certifies GoodWe Technologies Co Ltd: GEP96-1-US30 {208V} (grid-tied PV inverter, active in CEC directory) at 8,301 W AC (3,301 W above the 5,000 W 208 V median). Its 500 V DC ceiling pairs with an MPPT window of 182-500 V (span 318.0 V). Under NEC 690.8/705.12, 125% sizing demands 8 AWG Cu conductors on a 50 A OCPD.

## Where Does GoodWe Technologies Co Ltd: GEP96-1-US30 {208V} Fall Across Listed CEC Models?

Position of GoodWe Technologies Co Ltd: GEP96-1-US30 {208V} (8,301 W AC) relative to the 7,680 W CEC median inverter.

## What Dataset Percentiles Define GoodWe Technologies Co Ltd: GEP96-1-US30 {208V}?

Percentile placement of GoodWe Technologies Co Ltd: GEP96-1-US30 {208V} across AC power class, conversion efficiency, and backfeed breaker size.

## What Do the Dataset Ranks Show for GoodWe Technologies Co Ltd: GEP96-1-US30 {208V}?

Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for GoodWe Technologies Co Ltd: GEP96-1-US30 {208V}.

Eff #1,938 / 2,343

### 96.03% CEC Weighted Efficiency

-0.38 pts vs the 96.41% 208 V median; overall power rank #1,084 (8,301 W, top 46.3%; higher than 53.7% of peers).

NEC 705.12 Check

### 50 A Required Backfeed OCPD

125% x 39.9 A = 49.9 A -> 50 A standard OCPD using 8 AWG Cu (75 C).

MPPT Window

### 182 V - 500 V (Max 500 V DC)

Tracking span of 318.0 V; active in CEC directory (grid-tied PV inverter).

Commercial / 3-Phase Fit

### PASS (120% Commercial Busbar)

Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 8301.0W / 208 V -> 39.9 A | Breaker >= 1.25 * 39.9 = 49.9 A -> 50 A

CEC Inverters.csv for GoodWe Technologies Co Ltd: GEP96-1-US30 {208V}: Paco=8301.0 W, Vac=208 V, Vdcmax=500.0 V, Eff=96.03%.

**Result:** Min 50 A breaker & 8 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for GoodWe Technologies Co Ltd: GEP96-1-US30 {208V}?

Official California Energy Commission electrical test parameters, AC voltage, and DC limits for GoodWe Technologies Co Ltd: GEP96-1-US30 {208V}.

Official California Energy Commission (NREL SAM) test parameters for GoodWe Technologies Co Ltd: GEP96-1-US30 {208V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 8,301 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 500 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 182 V - 500 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 26.1953 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 96.03% | Calculated AC/DC conversion ratio from CEC test protocol |
| **Inverter Topology** | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |

## What Switchgear Limits Apply to GoodWe Technologies Co Ltd: GEP96-1-US30 {208V} (208 V, commercial single-phase)?

Check whether GoodWe Technologies Co Ltd: GEP96-1-US30 {208V} (50 A breaker) fits without main breaker derate or supply-side taps.

Evaluates GoodWe Technologies Co Ltd: GEP96-1-US30 {208V} (50 A required OCPD at 208 V, commercial single-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (208V)** | 40 A | 50 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (208V)** | 80 A | 50 A | PASS (120% Commercial Busbar) |
| **600A Bus / 600A Main (208V)** | 120 A | 50 A | PASS (120% Commercial Busbar) |
| **800A Bus / 800A Main (208V)** | 160 A | 50 A | PASS (120% Commercial Busbar) |
| **1,200A Bus / 1,200A Main (208V)** | 240 A | 50 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With GoodWe Technologies Co Ltd: GEP96-1-US30 {208V}?

Verified cold-weather (-10 C) series module counts matched to GoodWe Technologies Co Ltd: GEP96-1-US30 {208V}'s 500 V DC ceiling.

Sampled CEC PV modules aligned within 182.0-500.0 V MPPT and 500.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 5 to 8 panels | 4.72 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 6 to 11 panels | 4.84 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 6 to 11 panels | 4.67 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 7 to 12 panels | 2.4 kW |

## Which Competing Grid-Support Inverters Compare to GoodWe Technologies Co Ltd: GEP96-1-US30 {208V}?

Alternative CEC inverters comparable to GoodWe Technologies Co Ltd: GEP96-1-US30 {208V}, including Altenergy Power System Inc: ELS-96 {208V} (8,308 W) at 208 V, commercial single-phase.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Altenergy Power System Inc: ELS-96 {208V}**](https://epri-peac.com/solar-equipment/inverters/altenergy-power-system-inc/altenergy-power-system-inc-els-96-208v/) Altenergy Power System Inc | 8,308 W | +7 W | 208.0 V | 60.0 V | 93.5% |
| [**Delta Electronics: E10-TL-US(AC) {208V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-e10-tl-us-ac-208v/) Delta Electronics | 8,327 W | +26 W | 208.0 V | 480.0 V | 97.45% |
| [**Delta Electronics: M10-TL-US {208V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-m10-tl-us-208v/) Delta Electronics | 8,360 W | +59 W | 208.0 V | 480.0 V | 96.83% |
| [**Delta Electronics: M10-4-TL-US {208V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-m10-4-tl-us-208v/) Delta Electronics | 8,385 W | +84 W | 208.0 V | 480.0 V | 96.94% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for GoodWe Technologies Co Ltd: GEP96-1-US30 {208V}?

Check GoodWe Technologies Co Ltd: GEP96-1-US30 {208V} (8,301 W AC, 50 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 500 V DC on GoodWe Technologies Co Ltd: GEP96-1-US30 {208V}.

### GoodWe Technologies Co Ltd: GEP96-1-US30 {208V} Panel & Wire Spec

Size 75 C copper conductors at 8 AWG Cu on a 50 A OCPD breaker (39.9 A continuous).

### Alternative Inverter Comparison

Compare efficiency (96.03%) and MPPT window (182-500 V) directly against Altenergy Power System Inc: ELS-96 {208V} (8,308 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for GoodWe Technologies Co Ltd: GEP96-1-US30 {208V} by GoodWe Technologies Co Ltd covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.

### What breaker and wire size does GoodWe Technologies Co Ltd: GEP96-1-US30 {208V} require?

At 8,301 W continuous AC (208 V, commercial single-phase), continuous current is 39.9 A; 125% NEC 690.8/705.12 sizing requires a 50 A breaker and 8 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does GoodWe Technologies Co Ltd: GEP96-1-US30 {208V} require?

At 8,301 W AC and 208 V, commercial single-phase, continuous line current is 39.9 A, requiring a 50 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.

### How does GoodWe Technologies Co Ltd: GEP96-1-US30 {208V} compare to Altenergy Power System Inc: ELS-96 {208V}?

GoodWe Technologies Co Ltd: GEP96-1-US30 {208V} delivers 8,301 W AC at 96.03% CEC efficiency with a 500 V DC ceiling, while Altenergy Power System Inc: ELS-96 {208V} outputs 8,308 W at 208 V, commercial single-phase.

## Related Pages

Explore GoodWe Technologies Co Ltd hardware, Altenergy Power System Inc: ELS-96 {208V}, utility rates, and NEC 705.12 sizing calculators alongside GoodWe Technologies Co Ltd: GEP96-1-US30 {208V}.

[All GoodWe Technologies Co Ltd Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/goodwe-technologies-co-ltd/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From GoodWe Technologies Co Ltd

- [All GoodWe Technologies Co Ltd Specs](https://epri-peac.com/solar-equipment/brands/goodwe-technologies-co-ltd/)
- [GoodWe Technologies Co Ltd: GW60K-SMT-US {480V}](https://epri-peac.com/solar-equipment/inverters/goodwe-technologies-co-ltd/goodwe-technologies-co-ltd-gw60k-smt-us-480v/)
- [GoodWe Technologies Co Ltd: GW50K-SMT-US {480V}](https://epri-peac.com/solar-equipment/inverters/goodwe-technologies-co-ltd/goodwe-technologies-co-ltd-gw50k-smt-us-480v/)
- [GoodWe Technologies Co Ltd: GW28KLV-SMT-US {240V}](https://epri-peac.com/solar-equipment/inverters/goodwe-technologies-co-ltd/goodwe-technologies-co-ltd-gw28klv-smt-us-240v/)
- [GoodWe Technologies Co Ltd: GW28KLV-SMT-US {208V}](https://epri-peac.com/solar-equipment/inverters/goodwe-technologies-co-ltd/goodwe-technologies-co-ltd-gw28klv-smt-us-208v/)
- [GoodWe Technologies Co Ltd: GW22KLV-SMT-US {240V}](https://epri-peac.com/solar-equipment/inverters/goodwe-technologies-co-ltd/goodwe-technologies-co-ltd-gw22klv-smt-us-240v/)