---
title: "Ginlong Technologies Co Ltd Inverter (11,406W)"
url: https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-s6-eh1p114k-h-us-240v/
description: "CEC specs for Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V}: 11,406W AC, 240V, 60A OCPD, and NEC 705.12 checks. Source-verified US engineering data."
---

CEC Grid-Support Inverter

# Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V} — CEC Inverter Specifications

Manufacturer: [**Ginlong Technologies Co Ltd**](https://epri-peac.com/solar-equipment/brands/ginlong-technologies-co-ltd/) Registry: **CEC Verified Engineering Specification**

Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V} outputs 11,406 W AC at 240 V (47.5 A continuous, 60 A OCPD), ranking #608 of 2,343 CEC inverters at 97.4% efficiency with a 245-450 V MPPT window and 450 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 11,406 W

- **AC Voltage** : 240 V

- **Min PV Breaker** : 60 A (6 AWG Cu)

- **CEC Efficiency** : 97.4%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V} Compare Against Peer CEC Listings?

NEC 705.12 breaker requirements, efficiency placement, and 240 V grid-support overview for Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V}.

Rated at 11,406 W AC (47.5 A continuous), Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V} ranks #608 of 2,343 CEC units at 97.4% efficiency (+0.72 pts vs the 96.68% 240 V median). Minimum 75 C copper conductor sizing for its 60 A circuit is 6 AWG Cu per NEC Table 310.16. Cold-weather string Voc must remain under 450 V DC at record local winter lows.

## Where Does Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V} Fall Across Listed CEC Models?

Marks Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V} (11,406 W AC) across the California Energy Commission inverter AC capacity distribution.

## What Dataset Percentiles Define Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V}?

Benchmarks Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V} continuous AC output, 97.4% CEC weighted efficiency, and 60 A OCPD breaker demand.

## What Do the Dataset Ranks Show for Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V}?

Four key NEC 705.12 and California Energy Commission metrics defining Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V} by Ginlong Technologies Co Ltd.

Eff #608 / 2,343

### 97.4% CEC Weighted Efficiency

+0.72 pts vs the 96.68% 240 V median; overall power rank #777 (11,406 W, top 33.2%; higher than 66.8% of peers).

NEC 705.12 Check

### 60 A Required Backfeed OCPD

125% x 47.5 A = 59.4 A -> 60 A standard OCPD using 6 AWG Cu (75 C).

MPPT Window

### 245 V - 450 V (Max 450 V DC)

Tracking span of 205.0 V; listed since 2025-06-11 (hybrid battery-capable inverter).

Panel Fit (240V)

### Needs Derate / Tap 705.11

200A/200A panel allows 40A PV backfeed; 200A/175A derate allows 65A; 225A/200A allows 70A.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 11406.0W / 240 V -> 47.5 A | Breaker >= 1.25 * 47.5 = 59.4 A -> 60 A

CEC Inverters.csv for Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V}: Paco=11406.0 W, Vac=240 V, Vdcmax=450.0 V, Eff=97.4%.

**Result:** Min 60 A breaker & 6 AWG Cu (75 C); 200A Bus / 200A Main: Needs Derate / Tap 705.11.

## What Are the Published CEC Specifications for Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V}?

Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V}.

Official California Energy Commission (NREL SAM) test parameters for Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 11,406 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 240 V | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 450 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 245 V - 450 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 30.8169 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 97.4% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2025-06-11 / Hybrid: Yes (Battery Capable) | Utility interconnection approval metadata |

## Can a Residential Panel Meet 120% Busbar Limits for Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V}?

Evaluates Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V} (60 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.

Evaluates Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V} (60 A required OCPD at 240 V) across standard distribution busbars.

| Panel Configuration | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **100A Bus / 100A Main** | 20 A | 60 A | Needs Derate / Tap 705.11 |
| **150A Bus / 150A Main** | 30 A | 60 A | Needs Derate / Tap 705.11 |
| **200A Bus / 200A Main** | 40 A | 60 A | Needs Derate / Tap 705.11 |
| **200A Bus / 175A Main** | 65 A | 60 A | PASS (120% Rule) |
| **225A Bus / 200A Main** | 70 A | 60 A | PASS (120% Rule) |

## Which CEC PV Module Strings Pair With Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V}?

Sample PV string lengths aligned within 245-450 V MPPT and 450 V DC max at -10 C. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

Sampled CEC PV modules aligned within 245.0-450.0 V MPPT and 450.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 6 to 8 panels | 4.72 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 8 to 10 panels | 4.4 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 8 to 10 panels | 4.25 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 9 to 11 panels | 2.2 kW |

## Which Competing Grid-Support Inverters Compare to Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V}?

Competing CEC grid-support inverters near 11,406 W AC and 240 V, led by Altenergy Power System Inc: ELS-114 {240V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Altenergy Power System Inc: ELS-114 {240V}**](https://epri-peac.com/solar-equipment/inverters/altenergy-power-system-inc/altenergy-power-system-inc-els-114-240v/) Altenergy Power System Inc | 11,415 W | +9 W | 240.0 V | 60.0 V | 93.08% |
| [**Chint Power Systems America: CPS ECH114KTL/US {240V}**](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-ech114ktl-us-240v/) Chint Power Systems America | 11,360 W | -46 W | 240.0 V | 480.0 V | 96.53% |
| [**Dyness Digital Energy Technology Co LTD: TX114K-HM {240V}**](https://epri-peac.com/solar-equipment/inverters/dyness-digital-energy-technology-co-ltd/dyness-digital-energy-technology-co-ltd-tx114k-hm-240v/) Dyness Digital Energy Technology Co LTD | 11,498 W | +92 W | 240.0 V | 500.0 V | 96.41% |
| [**Dyness Digital Energy Technology Co LTD: TX114K-AM {240V}**](https://epri-peac.com/solar-equipment/inverters/dyness-digital-energy-technology-co-ltd/dyness-digital-energy-technology-co-ltd-tx114k-am-240v/) Dyness Digital Energy Technology Co LTD | 11,519 W | +113 W | 240.0 V | 490.0 V | 96.21% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V}?

Check Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V} (11,406 W AC, 60 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Its 60 A backfeed breaker exceeds a 200A/200A panel's 40 A ceiling, requiring a 175 A main derate, 225 A busbar, or NEC 705.11 tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 450 V DC on Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V}.

### Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V} Panel & Wire Spec

Size 75 C copper conductors at 6 AWG Cu on a 60 A OCPD breaker (47.5 A continuous).

### Alternative Inverter Comparison

Compare efficiency (97.4%) and MPPT window (245-450 V) directly against Altenergy Power System Inc: ELS-114 {240V} (11,415 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V} by Ginlong Technologies Co Ltd covering breaker sizing, MPPT limits, and 240 V interconnection.

### What breaker and wire size does Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V} require?

At 11,406 W continuous AC (240 V), continuous current is 47.5 A; 125% NEC 690.8/705.12 sizing requires a 60 A breaker and 6 AWG Cu (75 C) wire.

### Does Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V} fit a 200 A main panel under the 120% busbar rule?

A 200 A busbar with a 200 A main allows 40 A of solar backfeed. Requiring 60 A at 240 V means Needs Derate / Tap 705.11.

### How does Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V} compare to Altenergy Power System Inc: ELS-114 {240V}?

Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V} delivers 11,406 W AC at 97.4% CEC efficiency with a 450 V DC ceiling, while Altenergy Power System Inc: ELS-114 {240V} outputs 11,415 W at 240 V.

## Related Pages

Explore Ginlong Technologies Co Ltd hardware, Altenergy Power System Inc: ELS-114 {240V}, utility rates, and NEC 705.12 sizing calculators alongside Ginlong Technologies Co Ltd: S6-EH1P114K-H-US {240V}.

[All Ginlong Technologies Co Ltd Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/ginlong-technologies-co-ltd/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From Ginlong Technologies Co Ltd

- [All Ginlong Technologies Co Ltd Specs](https://epri-peac.com/solar-equipment/brands/ginlong-technologies-co-ltd/)
- [Ginlong Technologies Co Ltd: S6-GU350K-EHV-US-M16 {800V}](https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-s6-gu350k-ehv-us-m16-800v/)
- [Ginlong Technologies Co Ltd: S6-GU350K-EHV-US-M12 {800V}](https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-s6-gu350k-ehv-us-m12-800v/)
- [Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US {800V}](https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-solis-255k-ehv-5g-us-800v/)
- [Ginlong Technologies Co Ltd: S6-GU250K-EHV-US-M12 {600V}](https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-s6-gu250k-ehv-us-m12-600v/)
- [Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}](https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-solis-255k-ehv-5g-us-plus-800v/)
