title: "Ginlong Technologies Co Ltd Inverter (59,996W)"
url: https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-s5-gc60k-lv-us-208v/
description: "CEC specs for Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V}: 59,996W AC, 208V, 225A OCPD, and NEC 705.12 checks. Source-verified US engineering data."
---

CEC Grid-Support Inverter

# Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V} — CEC Inverter Specifications

Manufacturer: [**Ginlong Technologies Co Ltd**](https://epri-peac.com/solar-equipment/brands/ginlong-technologies-co-ltd/) Registry: **CEC Verified Engineering Specification**

Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V} outputs 59,996 W AC at 208 V, 3-phase (166.5 A continuous, 225 A OCPD), ranking #335 of 2,343 CEC inverters at 98.03% efficiency with a 400-650 V MPPT window and 650 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 59,996 W

- **AC Voltage** : 208 V, 3-phase

- **Min PV Breaker** : 225 A (4/0 AWG Cu)

- **CEC Efficiency** : 98.03%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V} Compare Against Peer CEC Listings?

How Ginlong Technologies Co Ltd Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V} compares on 98.03% efficiency, MPPT span, and 120% busbar interconnection.

With a 400-650 V MPPT tracking band and 650 V DC ceiling, Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V} handles 59,996 W continuous AC (54,996 W above the 5,000 W 208 V median). Commercial 208 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap. Installers comparing Ginlong Technologies Co Ltd against Chint Power Systems America: SCA50K-T-US-208 {208V} (50,000 W) should verify whether active in CEC directory grid-support firmware meets local IEEE 1547 utility rules.

## Where Does Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V} Fall Across Listed CEC Models?

Position of Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V} (59,996 W AC) relative to the 7,680 W CEC median inverter.

## What Dataset Percentiles Define Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V}?

Percentile placement of Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V} across AC power class, conversion efficiency, and backfeed breaker size.

## What Do the Dataset Ranks Show for Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V}?

Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V}.

Eff #335 / 2,343

### 98.03% CEC Weighted Efficiency

+1.62 pts vs the 96.41% 208 V median; overall power rank #419 (59,996 W, top 17.9%; higher than 82.1% of peers).

NEC 705.12 Check

### 225 A Required Backfeed OCPD

125% x 166.5 A = 208.1 A -> 225 A standard OCPD using 4/0 AWG Cu (75 C).

MPPT Window

### 400 V - 650 V (Max 650 V DC)

Tracking span of 250.0 V; active in CEC directory (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 208 V, 3-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 59996.0W / 208 V 3-phase -> 166.5 A | Breaker >= 1.25 * 166.5 = 208.1 A -> 225 A

CEC Inverters.csv for Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V}: Paco=59996.0 W, Vac=208 V, Vdcmax=650.0 V, Eff=98.03%.

**Result:** Min 225 A breaker & 4/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V}?

Official California Energy Commission electrical test parameters, AC voltage, and DC limits for Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V}.

Official California Energy Commission (NREL SAM) test parameters for Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 59,996 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 208 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 650 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 400 V - 650 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 130.22 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 98.03% | Calculated AC/DC conversion ratio from CEC test protocol |
| **Inverter Topology** | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |

## What Switchgear Limits Apply to Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V} (208 V, 3-phase)?

Check whether Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V} (225 A breaker) fits without main breaker derate or supply-side taps.

Evaluates Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V} (225 A required OCPD at 208 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (208V)** | 40 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (208V)** | 80 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (208V)** | 120 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (208V)** | 160 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (208V)** | 240 A | 225 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V}?

Verified cold-weather (-10 C) series module counts matched to Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V}'s 650 V DC ceiling.

Sampled CEC PV modules aligned within 400.0-650.0 V MPPT and 650.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 10 to 11 panels | 6.49 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 12 to 15 panels | 6.6 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 12 to 14 panels | 5.95 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 14 to 16 panels | 3.2 kW |

## Which Competing Grid-Support Inverters Compare to Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V}?

Alternative CEC inverters comparable to Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V}, including Chint Power Systems America: SCA50K-T-US-208 {208V} (50,000 W) at 208 V, 3-phase.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Chint Power Systems America: SCA50K-T-US-208 {208V}**](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-sca50k-t-us-208-208v/) Chint Power Systems America | 50,000 W | -9996 W | 208.0 V | 700.0 V | 95.93% |
| [**CSI Solar Co Ltd: CSI-30K-T208GL03-U {208V}**](https://epri-peac.com/solar-equipment/inverters/csi-solar-co-ltd/csi-solar-co-ltd-csi-30k-t208gl03-u-208v/) CSI Solar Co Ltd | 29,878 W | -30118 W | 208.0 V | 680.0 V | 96.38% |
| [**Chint Power Systems America: CPS SCA25KTL-DO/US-208 {208V}**](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-sca25ktl-do-us-208-208v/) Chint Power Systems America | 25,000 W | -34996 W | 208.0 V | 850.0 V | 96.26% |
| [**EcoFlow Inc: EF-PCS-24 {208V 24kW}**](https://epri-peac.com/solar-equipment/inverters/ecoflow-inc/ecoflow-inc-ef-pcs-24-208v-24kw/) EcoFlow Inc | 24,291 W | -35705 W | 208.0 V | 480.0 V | 96.01% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V}?

Check Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V} (59,996 W AC, 225 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 650 V DC on Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V}.

### Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V} Panel & Wire Spec

Size 75 C copper conductors at 4/0 AWG Cu on a 225 A OCPD breaker (166.5 A continuous).

### Alternative Inverter Comparison

Compare efficiency (98.03%) and MPPT window (400-650 V) directly against Chint Power Systems America: SCA50K-T-US-208 {208V} (50,000 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V} by Ginlong Technologies Co Ltd covering breaker sizing, MPPT limits, and 208 V, 3-phase interconnection.

### What breaker and wire size does Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V} require?

At 59,996 W continuous AC (208 V, 3-phase), continuous current is 166.5 A; 125% NEC 690.8/705.12 sizing requires a 225 A breaker and 4/0 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V} require?

At 59,996 W AC and 208 V, 3-phase, continuous line current is 166.5 A, requiring a 225 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.

### How does Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V} compare to Chint Power Systems America: SCA50K-T-US-208 {208V}?

Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V} delivers 59,996 W AC at 98.03% CEC efficiency with a 650 V DC ceiling, while Chint Power Systems America: SCA50K-T-US-208 {208V} outputs 50,000 W at 208 V, 3-phase.

## Related Pages

Explore Ginlong Technologies Co Ltd hardware, Chint Power Systems America: SCA50K-T-US-208 {208V}, utility rates, and NEC 705.12 sizing calculators alongside Ginlong Technologies Co Ltd: S5-GC60K-LV-US {208V}.

[All Ginlong Technologies Co Ltd Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/ginlong-technologies-co-ltd/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From Ginlong Technologies Co Ltd

- [All Ginlong Technologies Co Ltd Specs](https://epri-peac.com/solar-equipment/brands/ginlong-technologies-co-ltd/)
- [Ginlong Technologies Co Ltd: S6-GU350K-EHV-US-M16 {800V}](https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-s6-gu350k-ehv-us-m16-800v/)
- [Ginlong Technologies Co Ltd: S6-GU350K-EHV-US-M12 {800V}](https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-s6-gu350k-ehv-us-m12-800v/)
- [Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US {800V}](https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-solis-255k-ehv-5g-us-800v/)
- [Ginlong Technologies Co Ltd: S6-GU250K-EHV-US-M12 {600V}](https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-s6-gu250k-ehv-us-m12-600v/)
- [Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}](https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-solis-255k-ehv-5g-us-plus-800v/)