title: "Generac Power Systems Inc Inverter (11,748W)"
url: https://epri-peac.com/solar-equipment/inverters/generac-power-systems-inc/generac-power-systems-inc-xvt114g03-208v/
description: "CEC specs for Generac Power Systems Inc: XVT114G03 {208V}: 11,748W AC, 208V, 80A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# Generac Power Systems Inc: XVT114G03 {208V} — CEC Inverter Specifications

Manufacturer: [**Generac Power Systems Inc**](https://epri-peac.com/solar-equipment/brands/generac-power-systems-inc/) Registry: **CEC Verified Engineering Specification**

Generac Power Systems Inc: XVT114G03 {208V} outputs 11,748 W AC at 208 V, commercial single-phase (56.5 A continuous, 80 A OCPD), ranking #782 of 2,343 CEC inverters at 97.19% efficiency with a 390-420 V MPPT window and 420 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 11,748 W

- **AC Voltage** : 208 V, commercial single-phase

- **Min PV Breaker** : 80 A (4 AWG Cu)

- **CEC Efficiency** : 97.19%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Generac Power Systems Inc: XVT114G03 {208V} Compare Against Peer CEC Listings?

CEC efficiency rank (#782), 390-420 V MPPT tracking, and panel fit for Generac Power Systems Inc: XVT114G03 {208V}.

Generac Power Systems Inc: XVT114G03 {208V} from Generac Power Systems Inc outputs 56.5 A continuous AC at 208 V, commercial single-phase (11,748 W AC, rank #749). Paired with 4 AWG Cu conductors and an 80 A OCPD, its 97.19% CEC efficiency compares closely with Chint Power Systems America: CPS ECH12KTL/US {208V} (12,000 W). Keep NEC 690.7 winter string Voc below 420 V DC.

## Where Does Generac Power Systems Inc: XVT114G03 {208V} Fall Across Listed CEC Models?

CEC inverter wattage histogram highlighting Generac Power Systems Inc: XVT114G03 {208V} at 11,748 W continuous AC output. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.

## What Dataset Percentiles Define Generac Power Systems Inc: XVT114G03 {208V}?

Dataset percentiles comparing Generac Power Systems Inc: XVT114G03 {208V} against 2,343 certified grid-support inverters nationwide. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.

## What Do the Dataset Ranks Show for Generac Power Systems Inc: XVT114G03 {208V}?

Engineering highlights for Generac Power Systems Inc: XVT114G03 {208V} covering efficiency, 4 AWG Cu feeder, and panel compatibility.

Eff #782 / 2,343

### 97.19% CEC Weighted Efficiency

+0.78 pts vs the 96.41% 208 V median; overall power rank #749 (11,748 W, top 32.0%; higher than 68.0% of peers).

NEC 705.12 Check

### 80 A Required Backfeed OCPD

125% x 56.5 A = 70.6 A -> 80 A standard OCPD using 4 AWG Cu (75 C).

MPPT Window

### 390 V - 420 V (Max 420 V DC)

Tracking span of 30.0 V; listed since 2021-04-01 (hybrid battery-capable inverter).

Commercial / 3-Phase Fit

### PASS (120% Commercial Busbar)

Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 11748.0W / 208 V -> 56.5 A | Breaker >= 1.25 * 56.5 = 70.6 A -> 80 A

CEC Inverters.csv for Generac Power Systems Inc: XVT114G03 {208V}: Paco=11748.0 W, Vac=208 V, Vdcmax=420.0 V, Eff=97.19%.

**Result:** Min 80 A breaker & 4 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for Generac Power Systems Inc: XVT114G03 {208V}?

California Energy Commission Solar Equipment List parameters for Generac Power Systems Inc: XVT114G03 {208V} (hybrid battery-capable inverter) interconnection.

Official California Energy Commission (NREL SAM) test parameters for Generac Power Systems Inc: XVT114G03 {208V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 11,748 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 420 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 390 V - 420 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 30.2193 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 97.19% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2021-04-01 / Hybrid: Yes (Battery Capable) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to Generac Power Systems Inc: XVT114G03 {208V} (208 V, commercial single-phase)?

Panelboard and switchgear backfeed allowances for Generac Power Systems Inc: XVT114G03 {208V} (80 A OCPD). Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Evaluates Generac Power Systems Inc: XVT114G03 {208V} (80 A required OCPD at 208 V, commercial single-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (208V)** | 40 A | 80 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (208V)** | 80 A | 80 A | PASS (120% Commercial Busbar) |
| **600A Bus / 600A Main (208V)** | 120 A | 80 A | PASS (120% Commercial Busbar) |
| **800A Bus / 800A Main (208V)** | 160 A | 80 A | PASS (120% Commercial Busbar) |
| **1,200A Bus / 1,200A Main (208V)** | 240 A | 80 A | PASS (120% Commercial Busbar) |

## Which Competing Grid-Support Inverters Compare to Generac Power Systems Inc: XVT114G03 {208V}?

Four alternative CEC inverters matched to Generac Power Systems Inc: XVT114G03 {208V} (11,748 W AC), led by Chint Power Systems America: CPS ECH12KTL/US {208V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Chint Power Systems America: CPS ECH12KTL/US {208V}**](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-ech12ktl-us-208v/) Chint Power Systems America | 12,000 W | +252 W | 208.0 V | 480.0 V | 96.63% |
| [**EcoFlow Inc: EF-PCS-24 {208V 115kW}**](https://epri-peac.com/solar-equipment/inverters/ecoflow-inc/ecoflow-inc-ef-pcs-24-208v-115kw/) EcoFlow Inc | 11,444 W | -304 W | 208.0 V | 480.0 V | 96.52% |
| [**Chint Power Systems America: CPS ECH114KTL/US {208V}**](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-ech114ktl-us-208v/) Chint Power Systems America | 11,350 W | -398 W | 208.0 V | 480.0 V | 96.63% |
| [**EG4 Electronics LLC: IV-13000-HYB-AW-FX-xx {208V}**](https://epri-peac.com/solar-equipment/inverters/eg4-electronics-llc/eg4-electronics-llc-iv-13000-hyb-aw-fx-xx-208v/) EG4 Electronics LLC | 11,325 W | -423 W | 208.0 V | 440.0 V | 96.79% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for Generac Power Systems Inc: XVT114G03 {208V}?

Check Generac Power Systems Inc: XVT114G03 {208V} (11,748 W AC, 80 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 420 V DC on Generac Power Systems Inc: XVT114G03 {208V}.

### Generac Power Systems Inc: XVT114G03 {208V} Panel & Wire Spec

Size 75 C copper conductors at 4 AWG Cu on an 80 A OCPD breaker (56.5 A continuous).

### Alternative Inverter Comparison

Compare efficiency (97.19%) and MPPT window (390-420 V) directly against Chint Power Systems America: CPS ECH12KTL/US {208V} (12,000 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Generac Power Systems Inc: XVT114G03 {208V} by Generac Power Systems Inc covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.

### What breaker and wire size does Generac Power Systems Inc: XVT114G03 {208V} require?

At 11,748 W continuous AC (208 V, commercial single-phase), continuous current is 56.5 A; 125% NEC 690.8/705.12 sizing requires an 80 A breaker and 4 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does Generac Power Systems Inc: XVT114G03 {208V} require?

At 11,748 W AC and 208 V, commercial single-phase, continuous line current is 56.5 A, requiring an 80 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.

### How does Generac Power Systems Inc: XVT114G03 {208V} compare to Chint Power Systems America: CPS ECH12KTL/US {208V}?

Generac Power Systems Inc: XVT114G03 {208V} delivers 11,748 W AC at 97.19% CEC efficiency with a 420 V DC ceiling, while Chint Power Systems America: CPS ECH12KTL/US {208V} outputs 12,000 W at 208 V, commercial single-phase.

## Related Pages

Explore Generac Power Systems Inc hardware, Chint Power Systems America: CPS ECH12KTL/US {208V}, utility rates, and NEC 705.12 sizing calculators alongside Generac Power Systems Inc: XVT114G03 {208V}.

[All Generac Power Systems Inc Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/generac-power-systems-inc/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From Generac Power Systems Inc

- [All Generac Power Systems Inc Specs](https://epri-peac.com/solar-equipment/brands/generac-power-systems-inc/)
- [Generac Power Systems Inc: APKE00075 {240V}](https://epri-peac.com/solar-equipment/inverters/generac-power-systems-inc/generac-power-systems-inc-apke00075-240v/)
- [Generac Power Systems Inc: X11402 {208V}](https://epri-peac.com/solar-equipment/inverters/generac-power-systems-inc/generac-power-systems-inc-x11402-208v/)
- [Generac Power Systems Inc: XVT076A03 {240V}](https://epri-peac.com/solar-equipment/inverters/generac-power-systems-inc/generac-power-systems-inc-xvt076a03-240v/)
- [Generac Power Systems Inc: X7602 {240V}](https://epri-peac.com/solar-equipment/inverters/generac-power-systems-inc/generac-power-systems-inc-x7602-240v/)
- [Generac Power Systems Inc: PM-820 {208V}](https://epri-peac.com/solar-equipment/inverters/generac-power-systems-inc/generac-power-systems-inc-pm-820-208v/)