CEC Grid-Support Inverter

# EPC Power Corp: 50-200100 {850V} — CEC Inverter Specifications

Manufacturer: [**EPC Power Corp**](https://epri-peac.com/solar-equipment/brands/epc-power-corp/) Registry: **CEC Verified Engineering Specification**

EPC Power Corp: 50-200100 {850V} outputs 663,578 W AC at 850 V, 3-phase (450.7 A continuous, 600 A OCPD), ranking #26 of 2,343 CEC inverters at 98.77% efficiency with a 1,388-1,500 V MPPT window and 1,500 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 663,578 W

- **AC Voltage** : 850 V, 3-phase

- **Min PV Breaker** : 600 A (parallel Cu feeders)

- **CEC Efficiency** : 98.77%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does EPC Power Corp: 50-200100 {850V} Compare Against Peer CEC Listings?

How EPC Power Corp EPC Power Corp: 50-200100 {850V} compares on 98.77% efficiency, MPPT span, and 120% busbar interconnection.

With a 1,388-1,500 V MPPT tracking band and 1,500 V DC ceiling, EPC Power Corp: 50-200100 {850V} handles 663,578 W continuous AC (equal to the 663,578 W 850 V median). Commercial 850 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (850V) or NEC 705.11 supply-side tap. Installers comparing EPC Power Corp against ABB: PVS-175-TL-POWER-MODULE-1-US {800V} (179,574 W) should verify whether active in CEC directory grid-support firmware meets local IEEE 1547 utility rules.

## Where Does EPC Power Corp: 50-200100 {850V} Fall Across Listed CEC Models?

Position of EPC Power Corp: 50-200100 {850V} (663,578 W AC) relative to the 7,680 W CEC median inverter.

## What Dataset Percentiles Define EPC Power Corp: 50-200100 {850V}?

Percentile placement of EPC Power Corp: 50-200100 {850V} across AC power class, conversion efficiency, and backfeed breaker size.

## What Do the Dataset Ranks Show for EPC Power Corp: 50-200100 {850V}?

Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for EPC Power Corp: 50-200100 {850V}. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.

Eff #26 / 2,343

### 98.77% CEC Weighted Efficiency

equal to the 98.77% 850 V median; overall power rank #186 (663,578 W, top 7.9%; higher than 92.1% of peers).

NEC 705.12 Check

### 600 A Required Backfeed OCPD

125% x 450.7 A = 563.4 A -> 600 A standard OCPD using parallel Cu feeders (75 C).

MPPT Window

### 1,388 V - 1,500 V (Max 1,500 V DC)

Tracking span of 112.0 V; active in CEC directory (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 850 V, 3-phase switchgear (200A Bus / 200A Main (850V) to 1,200A Bus / 1,200A Main (850V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 663578.0W / 850 V 3-phase -> 450.7 A | Breaker >= 1.25 * 450.7 = 563.4 A -> 600 A

CEC Inverters.csv for EPC Power Corp: 50-200100 {850V}: Paco=663578.0 W, Vac=850 V, Vdcmax=1500.0 V, Eff=98.77%.

**Result:** Min 600 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (850V): Supply-Side Tap (705.11) / Dedicated Switchboard.

## What Are the Published CEC Specifications for EPC Power Corp: 50-200100 {850V}?

Official California Energy Commission electrical test parameters, AC voltage, and DC limits for EPC Power Corp: 50-200100 {850V}.

Official California Energy Commission (NREL SAM) test parameters for EPC Power Corp: 50-200100 {850V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 663,578 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 850 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 1,500 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 1,388 V - 1,500 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 465.256 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 98.77% | Calculated AC/DC conversion ratio from CEC test protocol |
| **Inverter Topology** | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |

## What Switchgear Limits Apply to EPC Power Corp: 50-200100 {850V} (850 V, 3-phase)?

Check whether EPC Power Corp: 50-200100 {850V} (600 A breaker) fits without main breaker derate or supply-side taps.

Evaluates EPC Power Corp: 50-200100 {850V} (600 A required OCPD at 850 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (850V)** | 40 A | 600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (850V)** | 80 A | 600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (850V)** | 120 A | 600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (850V)** | 160 A | 600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (850V)** | 240 A | 600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |

## Which Competing Grid-Support Inverters Compare to EPC Power Corp: 50-200100 {850V}?

Alternative CEC inverters comparable to EPC Power Corp: 50-200100 {850V}, including ABB: PVS-175-TL-POWER-MODULE-1-US {800V} (179,574 W) at 850 V, 3-phase.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**ABB: PVS-175-TL-POWER-MODULE-1-US {800V}**](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-175-tl-power-module-1-us-800v/) ABB | 179,574 W | -484004 W | 800.0 V | 1200.0 V | 97.39% |
| [**LS Energy Solutions LLC: PBE-6140-R61-1A0-1000 {600V}**](https://epri-peac.com/solar-equipment/inverters/ls-energy-solutions-llc/ls-energy-solutions-llc-pbe-6140-r61-1a0-1000-600v/) LS Energy Solutions LLC | 139,449 W | -524129 W | 600.0 V | 1350.0 V | 98.27% |
| [**JingTsing Technology Ltd: JTES-PCS125K-1000/480-L03C1 {480V}**](https://epri-peac.com/solar-equipment/inverters/jingtsing-technology-ltd/jingtsing-technology-ltd-jtes-pcs125k-1000-480-l03c1-480v/) JingTsing Technology Ltd | 127,819 W | -535759 W | 480.0 V | 950.0 V | 98.0% |
| [**SMA America: SHP FLEX-US-21 {385V}**](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-shp-flex-us-21-385v/) SMA America | 100,842 W | -562736 W | 385.0 V | 1195.0 V | 97.8% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for EPC Power Corp: 50-200100 {850V}?

Check EPC Power Corp: 50-200100 {850V} (663,578 W AC, 600 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 850 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (850V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,500 V DC on EPC Power Corp: 50-200100 {850V}.

### EPC Power Corp: 50-200100 {850V} Panel & Wire Spec

Size 75 C copper conductors at parallel Cu feeders on a 600 A OCPD breaker (450.7 A continuous).

### Alternative Inverter Comparison

Compare efficiency (98.77%) and MPPT window (1,388-1,500 V) directly against ABB: PVS-175-TL-POWER-MODULE-1-US {800V} (179,574 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for EPC Power Corp: 50-200100 {850V} by EPC Power Corp covering breaker sizing, MPPT limits, and 850 V, 3-phase interconnection.

### What breaker and wire size does EPC Power Corp: 50-200100 {850V} require?

At 663,578 W continuous AC (850 V, 3-phase), continuous current is 450.7 A; 125% NEC 690.8/705.12 sizing requires a 600 A breaker and parallel Cu feeders (75 C) wire.

### What commercial switchgear or feeder sizing does EPC Power Corp: 50-200100 {850V} require?

At 663,578 W AC and 850 V, 3-phase, continuous line current is 450.7 A, requiring a 600 A OCPD and 1,200A Bus / 1,200A Main (850V) or NEC 705.11 interconnection.

### How does EPC Power Corp: 50-200100 {850V} compare to ABB: PVS-175-TL-POWER-MODULE-1-US {800V}?

EPC Power Corp: 50-200100 {850V} delivers 663,578 W AC at 98.77% CEC efficiency with a 1,500 V DC ceiling, while ABB: PVS-175-TL-POWER-MODULE-1-US {800V} outputs 179,574 W at 850 V, 3-phase.

## Related Pages

Explore EPC Power Corp hardware, ABB: PVS-175-TL-POWER-MODULE-1-US {800V}, utility rates, and NEC 705.12 sizing calculators alongside EPC Power Corp: 50-200100 {850V}.

[All EPC Power Corp Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/epc-power-corp/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From EPC Power Corp

- [All EPC Power Corp Specs](https://epri-peac.com/solar-equipment/brands/epc-power-corp/)
- [EPC Power Corp: 50-100181 {690V}](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100181-690v/)
- [EPC Power Corp: 50-100100 {690V}](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100100-690v/)
- [EPC Power Corp: 50-100181 {600V}](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100181-600v/)
- [EPC Power Corp: 50-100181 {480V}](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100181-480v/)
- [EPC Power Corp: 50-100100 {480V}](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100100-480v/)