title: "EPC Power Corp: 50-200100 {660V} Inverter (515,072W)"
url: https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-200100-660v/
description: "CEC specs for EPC Power Corp: 50-200100 {660V}: 515,072W AC, 660V, 600A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# EPC Power Corp: 50-200100 {660V} — CEC Inverter Specifications

Manufacturer: [**EPC Power Corp**](https://epri-peac.com/solar-equipment/brands/epc-power-corp/) Registry: **CEC Verified Engineering Specification**

EPC Power Corp: 50-200100 {660V} outputs 515,072 W AC at 660 V, 3-phase (450.6 A continuous, 600 A OCPD), ranking #86 of 2,343 CEC inverters at 98.47% efficiency with a 1,083-1,500 V MPPT window and 1,500 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 515,072 W

- **AC Voltage** : 660 V, 3-phase

- **Min PV Breaker** : 600 A (parallel Cu feeders)

- **CEC Efficiency** : 98.47%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does EPC Power Corp: 50-200100 {660V} Compare Against Peer CEC Listings?

NEC 705.12 breaker requirements, efficiency placement, and 660 V, 3-phase grid-support overview for EPC Power Corp: 50-200100 {660V}.

Rated at 515,072 W AC (450.6 A continuous), EPC Power Corp: 50-200100 {660V} ranks #86 of 2,343 CEC units at 98.47% efficiency (+0.26 pts vs the 98.21% 660 V median). Minimum 75 C copper conductor sizing for its 600 A circuit is parallel Cu feeders per NEC Table 310.16. Cold-weather string Voc must remain under 1,500 V DC at record local winter lows.

## Where Does EPC Power Corp: 50-200100 {660V} Fall Across Listed CEC Models?

Marks EPC Power Corp: 50-200100 {660V} (515,072 W AC) across the California Energy Commission inverter AC capacity distribution.

## What Dataset Percentiles Define EPC Power Corp: 50-200100 {660V}?

Benchmarks EPC Power Corp: 50-200100 {660V} continuous AC output, 98.47% CEC weighted efficiency, and 600 A OCPD breaker demand.

## What Do the Dataset Ranks Show for EPC Power Corp: 50-200100 {660V}?

Four key NEC 705.12 and California Energy Commission metrics defining EPC Power Corp: 50-200100 {660V} by EPC Power Corp.

Eff #86 / 2,343

### 98.47% CEC Weighted Efficiency

+0.26 pts vs the 98.21% 660 V median; overall power rank #191 (515,072 W, top 8.2%; higher than 91.8% of peers).

NEC 705.12 Check

### 600 A Required Backfeed OCPD

125% x 450.6 A = 563.2 A -> 600 A standard OCPD using parallel Cu feeders (75 C).

MPPT Window

### 1,083 V - 1,500 V (Max 1,500 V DC)

Tracking span of 417.0 V; active in CEC directory (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 660 V, 3-phase switchgear (200A Bus / 200A Main (660V) to 1,200A Bus / 1,200A Main (660V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 515072.0W / 660 V 3-phase -> 450.6 A | Breaker >= 1.25 * 450.6 = 563.2 A -> 600 A

CEC Inverters.csv for EPC Power Corp: 50-200100 {660V}: Paco=515072.0 W, Vac=660 V, Vdcmax=1500.0 V, Eff=98.47%.

**Result:** Min 600 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (660V): Supply-Side Tap (705.11) / Dedicated Switchboard.

## What Are the Published CEC Specifications for EPC Power Corp: 50-200100 {660V}?

Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for EPC Power Corp: 50-200100 {660V}.

Official California Energy Commission (NREL SAM) test parameters for EPC Power Corp: 50-200100 {660V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 515,072 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 660 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 1,500 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 1,083 V - 1,500 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 405.006 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 98.47% | Calculated AC/DC conversion ratio from CEC test protocol |
| **Inverter Topology** | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |

## What Switchgear Limits Apply to EPC Power Corp: 50-200100 {660V} (660 V, 3-phase)?

Evaluates EPC Power Corp: 50-200100 {660V} (600 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.

Evaluates EPC Power Corp: 50-200100 {660V} (600 A required OCPD at 660 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (660V)** | 40 A | 600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (660V)** | 80 A | 600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (660V)** | 120 A | 600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (660V)** | 160 A | 600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (660V)** | 240 A | 600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |

## Which CEC PV Module Strings Pair With EPC Power Corp: 50-200100 {660V}?

Sample PV string lengths aligned within 1,083-1,500 V MPPT and 1,500 V DC max at -10 C. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.

Sampled CEC PV modules aligned within 1083.0-1500.0 V MPPT and 1500.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 26 panels (fixed) | 15.34 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 33 to 35 panels | 15.4 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 32 to 33 panels | 14.03 kW |
| [**Chint New Energy Technology Co Ltd CHSM72M(DG)/F-BH-515**](https://epri-peac.com/solar-equipment/modules/chint-new-energy-technology-co-ltd/chint-new-energy-technology-co-ltd-chsm72m-dg-f-bh-515/) | 515.0 W | 53.76 V | 27 panels (fixed) | 13.9 kW |

## Which Competing Grid-Support Inverters Compare to EPC Power Corp: 50-200100 {660V}?

Competing CEC grid-support inverters near 515,072 W AC and 660 V, 3-phase, led by SMA America: SHP FLEX-US-21 {660V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**SMA America: SHP FLEX-US-21 {660V}**](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-shp-flex-us-21-660v/) SMA America | 172,810 W | -342262 W | 660.0 V | 1200.0 V | 98.57% |
| [**SMA America: SHP 172-US-21 {660V}**](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-shp-172-us-21-660v/) SMA America | 172,000 W | -343072 W | 660.0 V | 1200.0 V | 98.57% |
| [**KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQ0 {660V}**](https://epri-peac.com/solar-equipment/inverters/kaco-new-energy-gmbh/kaco-new-energy-gmbh-kaco-blueplanet-150-tl3-m1-wm-od-iiq0-660v/) KACO new energy GmbH | 151,228 W | -363844 W | 660.0 V | 1300.0 V | 98.78% |
| [**KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V}**](https://epri-peac.com/solar-equipment/inverters/kaco-new-energy-gmbh/kaco-new-energy-gmbh-kaco-blueplanet-150-tl3-m1-wm-od-iiqx-660v/) KACO new energy GmbH | 151,228 W | -363844 W | 660.0 V | 1300.0 V | 98.78% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for EPC Power Corp: 50-200100 {660V}?

Check EPC Power Corp: 50-200100 {660V} (515,072 W AC, 600 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 660 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (660V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,500 V DC on EPC Power Corp: 50-200100 {660V}.

### EPC Power Corp: 50-200100 {660V} Panel & Wire Spec

Size 75 C copper conductors at parallel Cu feeders on a 600 A OCPD breaker (450.6 A continuous).

### Alternative Inverter Comparison

Compare efficiency (98.47%) and MPPT window (1,083-1,500 V) directly against SMA America: SHP FLEX-US-21 {660V} (172,810 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for EPC Power Corp: 50-200100 {660V} by EPC Power Corp covering breaker sizing, MPPT limits, and 660 V, 3-phase interconnection.

### What breaker and wire size does EPC Power Corp: 50-200100 {660V} require?

At 515,072 W continuous AC (660 V, 3-phase), continuous current is 450.6 A; 125% NEC 690.8/705.12 sizing requires a 600 A breaker and parallel Cu feeders (75 C) wire.

### What commercial switchgear or feeder sizing does EPC Power Corp: 50-200100 {660V} require?

At 515,072 W AC and 660 V, 3-phase, continuous line current is 450.6 A, requiring a 600 A OCPD and 1,200A Bus / 1,200A Main (660V) or NEC 705.11 interconnection.

### How does EPC Power Corp: 50-200100 {660V} compare to SMA America: SHP FLEX-US-21 {660V}?

EPC Power Corp: 50-200100 {660V} delivers 515,072 W AC at 98.47% CEC efficiency with a 1,500 V DC ceiling, while SMA America: SHP FLEX-US-21 {660V} outputs 172,810 W at 660 V, 3-phase.

## Related Pages

Explore EPC Power Corp hardware, SMA America: SHP FLEX-US-21 {660V}, utility rates, and NEC 705.12 sizing calculators alongside EPC Power Corp: 50-200100 {660V}.

[All EPC Power Corp Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/epc-power-corp/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From EPC Power Corp

- [All EPC Power Corp Specs](https://epri-peac.com/solar-equipment/brands/epc-power-corp/)
- [EPC Power Corp: 50-100181 {690V}](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100181-690v/)
- [EPC Power Corp: 50-100100 {690V}](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100100-690v/)
- [EPC Power Corp: 50-100181 {600V}](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100181-600v/)
- [EPC Power Corp: 50-100181 {480V}](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100181-480v/)
- [EPC Power Corp: 50-100100 {480V}](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100100-480v/)