title: "EPC Power Corp: 50-100122 {480V} Inverter (250,190W)"
url: https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100122-480v/
description: "CEC specs for EPC Power Corp: 50-100122 {480V}: 250,190W AC, 480V, 400A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# EPC Power Corp: 50-100122 {480V} — CEC Inverter Specifications

Manufacturer: [**EPC Power Corp**](https://epri-peac.com/solar-equipment/brands/epc-power-corp/) Registry: **CEC Verified Engineering Specification**

EPC Power Corp: 50-100122 {480V} outputs 250,190 W AC at 480 V, 3-phase (300.9 A continuous, 400 A OCPD), ranking #876 of 2,343 CEC inverters at 97.11% efficiency with a 710-1,250 V MPPT window and 1,250 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 250,190 W

- **AC Voltage** : 480 V, 3-phase

- **Min PV Breaker** : 400 A (parallel Cu feeders)

- **CEC Efficiency** : 97.11%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does EPC Power Corp: 50-100122 {480V} Compare Against Peer CEC Listings?

CEC efficiency rank (#876), 710-1,250 V MPPT tracking, and panel fit for EPC Power Corp: 50-100122 {480V}. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.

EPC Power Corp: 50-100122 {480V} from EPC Power Corp outputs 300.9 A continuous AC at 480 V, 3-phase (250,190 W AC, rank #224). Paired with parallel Cu feeders conductors and a 400 A OCPD, its 97.11% CEC efficiency compares closely with DYNAPOWER COMPANY LLC: MPS-250HV {480V} (249,619 W). Keep NEC 690.7 winter string Voc below 1,250 V DC.

## Where Does EPC Power Corp: 50-100122 {480V} Fall Across Listed CEC Models?

CEC inverter wattage histogram highlighting EPC Power Corp: 50-100122 {480V} at 250,190 W continuous AC output. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.

## What Dataset Percentiles Define EPC Power Corp: 50-100122 {480V}?

Dataset percentiles comparing EPC Power Corp: 50-100122 {480V} against 2,343 certified grid-support inverters nationwide. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.

## What Do the Dataset Ranks Show for EPC Power Corp: 50-100122 {480V}?

Engineering highlights for EPC Power Corp: 50-100122 {480V} covering efficiency, parallel Cu feeders feeder, and panel compatibility. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.

Eff #876 / 2,343

### 97.11% CEC Weighted Efficiency

-0.91 pts vs the 98.02% 480 V median; overall power rank #224 (250,190 W, top 9.6%; higher than 90.4% of peers).

NEC 705.12 Check

### 400 A Required Backfeed OCPD

125% x 300.9 A = 376.1 A -> 400 A standard OCPD using parallel Cu feeders (75 C).

MPPT Window

### 710 V - 1,250 V (Max 1,250 V DC)

Tracking span of 540.0 V; listed since 2021-05-03 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 250190.0W / 480 V 3-phase -> 300.9 A | Breaker >= 1.25 * 300.9 = 376.1 A -> 400 A

CEC Inverters.csv for EPC Power Corp: 50-100122 {480V}: Paco=250190.0 W, Vac=480 V, Vdcmax=1250.0 V, Eff=97.11%.

**Result:** Min 400 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (480V): Supply-Side Tap (705.11) / Dedicated Switchboard.

## What Are the Published CEC Specifications for EPC Power Corp: 50-100122 {480V}?

California Energy Commission Solar Equipment List parameters for EPC Power Corp: 50-100122 {480V} (grid-tied PV inverter) interconnection. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

Official California Energy Commission (NREL SAM) test parameters for EPC Power Corp: 50-100122 {480V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 250,190 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 1,250 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 710 V - 1,250 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 271.209 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 97.11% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2021-05-03 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to EPC Power Corp: 50-100122 {480V} (480 V, 3-phase)?

Panelboard and switchgear backfeed allowances for EPC Power Corp: 50-100122 {480V} (400 A OCPD). Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.

Evaluates EPC Power Corp: 50-100122 {480V} (400 A required OCPD at 480 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (480V)** | 40 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (480V)** | 80 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (480V)** | 120 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (480V)** | 160 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (480V)** | 240 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |

## Which CEC PV Module Strings Pair With EPC Power Corp: 50-100122 {480V}?

Representative PV panel pairings verified under NEC 690.7 cold Voc for EPC Power Corp: 50-100122 {480V}. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

Sampled CEC PV modules aligned within 710.0-1250.0 V MPPT and 1250.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 17 to 22 panels | 12.98 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 22 to 29 panels | 12.76 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 21 to 27 panels | 11.47 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 25 to 30 panels | 6.0 kW |

## Which Competing Grid-Support Inverters Compare to EPC Power Corp: 50-100122 {480V}?

Four alternative CEC inverters matched to EPC Power Corp: 50-100122 {480V} (250,190 W AC), led by DYNAPOWER COMPANY LLC: MPS-250HV {480V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**DYNAPOWER COMPANY LLC: MPS-250HV {480V}**](https://epri-peac.com/solar-equipment/inverters/dynapower-company-llc/dynapower-company-llc-mps-250hv-480v/) DYNAPOWER COMPANY LLC | 249,619 W | -571 W | 480.0 V | 830.0 V | 96.2% |
| [**DYNAPOWER COMPANY LLC: MPS-250 {480V}**](https://epri-peac.com/solar-equipment/inverters/dynapower-company-llc/dynapower-company-llc-mps-250-480v/) DYNAPOWER COMPANY LLC | 248,910 W | -1280 W | 480.0 V | 600.0 V | 95.24% |
| [**Chint Power Systems America: SCH200K-T-US-480 {480V}**](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-sch200k-t-us-480-480v/) Chint Power Systems America | 200,000 W | -50190 W | 480.0 V | 1300.0 V | 97.72% |
| [**Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V}**](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-ecb125ktl-m-us-480-480v/) Chint Power Systems America | 125,000 W | -125190 W | 480.0 V | 1100.0 V | 97.2% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for EPC Power Corp: 50-100122 {480V}?

Check EPC Power Corp: 50-100122 {480V} (250,190 W AC, 400 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,250 V DC on EPC Power Corp: 50-100122 {480V}.

### EPC Power Corp: 50-100122 {480V} Panel & Wire Spec

Size 75 C copper conductors at parallel Cu feeders on a 400 A OCPD breaker (300.9 A continuous).

### Alternative Inverter Comparison

Compare efficiency (97.11%) and MPPT window (710-1,250 V) directly against DYNAPOWER COMPANY LLC: MPS-250HV {480V} (249,619 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for EPC Power Corp: 50-100122 {480V} by EPC Power Corp covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.

### What breaker and wire size does EPC Power Corp: 50-100122 {480V} require?

At 250,190 W continuous AC (480 V, 3-phase), continuous current is 300.9 A; 125% NEC 690.8/705.12 sizing requires a 400 A breaker and parallel Cu feeders (75 C) wire.

### What commercial switchgear or feeder sizing does EPC Power Corp: 50-100122 {480V} require?

At 250,190 W AC and 480 V, 3-phase, continuous line current is 300.9 A, requiring a 400 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

### How does EPC Power Corp: 50-100122 {480V} compare to DYNAPOWER COMPANY LLC: MPS-250HV {480V}?

EPC Power Corp: 50-100122 {480V} delivers 250,190 W AC at 97.11% CEC efficiency with a 1,250 V DC ceiling, while DYNAPOWER COMPANY LLC: MPS-250HV {480V} outputs 249,619 W at 480 V, 3-phase.

## Related Pages

Explore EPC Power Corp hardware, DYNAPOWER COMPANY LLC: MPS-250HV {480V}, utility rates, and NEC 705.12 sizing calculators alongside EPC Power Corp: 50-100122 {480V}.

[All EPC Power Corp Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/epc-power-corp/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From EPC Power Corp

- [All EPC Power Corp Specs](https://epri-peac.com/solar-equipment/brands/epc-power-corp/)
- [EPC Power Corp: 50-100181 {690V}](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100181-690v/)
- [EPC Power Corp: 50-100100 {690V}](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100100-690v/)
- [EPC Power Corp: 50-100181 {600V}](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100181-600v/)
- [EPC Power Corp: 50-100181 {480V}](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100181-480v/)
- [EPC Power Corp: 50-100100 {480V}](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100100-480v/)