title: "DYNAPOWER COMPANY LLC: MPS-250 Inverter (248,910W)"
url: https://epri-peac.com/solar-equipment/inverters/dynapower-company-llc/dynapower-company-llc-mps-250-480v/
description: "CEC specs for DYNAPOWER COMPANY LLC: MPS-250 {480V}: 248,910W AC, 480V, 400A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# DYNAPOWER COMPANY LLC: MPS-250 {480V} — CEC Inverter Specifications

Manufacturer: [**DYNAPOWER COMPANY LLC**](https://epri-peac.com/solar-equipment/brands/dynapower-company-llc/) Registry: **CEC Verified Engineering Specification**

DYNAPOWER COMPANY LLC: MPS-250 {480V} outputs 248,910 W AC at 480 V, 3-phase (299.4 A continuous, 400 A OCPD), ranking #2,223 of 2,343 CEC inverters at 95.24% efficiency with a 350-600 V MPPT window and 600 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 248,910 W

- **AC Voltage** : 480 V, 3-phase

- **Min PV Breaker** : 400 A (parallel Cu feeders)

- **CEC Efficiency** : 95.24%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does DYNAPOWER COMPANY LLC: MPS-250 {480V} Compare Against Peer CEC Listings?

How DYNAPOWER COMPANY LLC DYNAPOWER COMPANY LLC: MPS-250 {480V} compares on 95.24% efficiency, MPPT span, and 120% busbar interconnection.

With a 350-600 V MPPT tracking band and 600 V DC ceiling, DYNAPOWER COMPANY LLC: MPS-250 {480V} handles 248,910 W continuous AC (198,910 W above the 50,000 W 480 V median). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap. Installers comparing DYNAPOWER COMPANY LLC against EPC Power Corp: 50-100122 {480V} (250,190 W) should verify whether listed since 2018-10-15 grid-support firmware meets local IEEE 1547 utility rules.

## Where Does DYNAPOWER COMPANY LLC: MPS-250 {480V} Fall Across Listed CEC Models?

Position of DYNAPOWER COMPANY LLC: MPS-250 {480V} (248,910 W AC) relative to the 7,680 W CEC median inverter.

## What Dataset Percentiles Define DYNAPOWER COMPANY LLC: MPS-250 {480V}?

Percentile placement of DYNAPOWER COMPANY LLC: MPS-250 {480V} across AC power class, conversion efficiency, and backfeed breaker size.

## What Do the Dataset Ranks Show for DYNAPOWER COMPANY LLC: MPS-250 {480V}?

Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for DYNAPOWER COMPANY LLC: MPS-250 {480V}. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

Eff #2,223 / 2,343

### 95.24% CEC Weighted Efficiency

-2.78 pts vs the 98.02% 480 V median; overall power rank #232 (248,910 W, top 9.9%; higher than 90.1% of peers).

NEC 705.12 Check

### 400 A Required Backfeed OCPD

125% x 299.4 A = 374.2 A -> 400 A standard OCPD using parallel Cu feeders (75 C).

MPPT Window

### 350 V - 600 V (Max 600 V DC)

Tracking span of 250.0 V; listed since 2018-10-15 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 248910.0W / 480 V 3-phase -> 299.4 A | Breaker >= 1.25 * 299.4 = 374.2 A -> 400 A

CEC Inverters.csv for DYNAPOWER COMPANY LLC: MPS-250 {480V}: Paco=248910.0 W, Vac=480 V, Vdcmax=600.0 V, Eff=95.24%.

**Result:** Min 400 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (480V): Supply-Side Tap (705.11) / Dedicated Switchboard.

## What Are the Published CEC Specifications for DYNAPOWER COMPANY LLC: MPS-250 {480V}?

Official California Energy Commission electrical test parameters, AC voltage, and DC limits for DYNAPOWER COMPANY LLC: MPS-250 {480V}.

Official California Energy Commission (NREL SAM) test parameters for DYNAPOWER COMPANY LLC: MPS-250 {480V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 248,910 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 600 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 350 V - 600 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 550.189 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 95.24% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2018-10-15 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to DYNAPOWER COMPANY LLC: MPS-250 {480V} (480 V, 3-phase)?

Check whether DYNAPOWER COMPANY LLC: MPS-250 {480V} (400 A breaker) fits without main breaker derate or supply-side taps.

Evaluates DYNAPOWER COMPANY LLC: MPS-250 {480V} (400 A required OCPD at 480 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (480V)** | 40 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (480V)** | 80 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (480V)** | 120 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (480V)** | 160 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (480V)** | 240 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |

## Which CEC PV Module Strings Pair With DYNAPOWER COMPANY LLC: MPS-250 {480V}?

Verified cold-weather (-10 C) series module counts matched to DYNAPOWER COMPANY LLC: MPS-250 {480V}'s 600 V DC ceiling.

Sampled CEC PV modules aligned within 350.0-600.0 V MPPT and 600.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 9 to 10 panels | 5.9 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 11 to 14 panels | 6.16 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 11 to 13 panels | 5.53 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 13 to 14 panels | 2.8 kW |

## Which Competing Grid-Support Inverters Compare to DYNAPOWER COMPANY LLC: MPS-250 {480V}?

Alternative CEC inverters comparable to DYNAPOWER COMPANY LLC: MPS-250 {480V}, including EPC Power Corp: 50-100122 {480V} (250,190 W) at 480 V, 3-phase.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**EPC Power Corp: 50-100122 {480V}**](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100122-480v/) EPC Power Corp | 250,190 W | +1280 W | 480.0 V | 1250.0 V | 97.11% |
| [**EPC Power Corp: 50-100205 {480V}**](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100205-480v/) EPC Power Corp | 250,190 W | +1280 W | 480.0 V | 1250.0 V | 97.11% |
| [**EPC Power Corp: HY LC12/6-7 {480V}**](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-hy-lc12-6-7-480v/) EPC Power Corp | 220,033 W | -28877 W | 480.0 V | 600.0 V | 95.51% |
| [**Chint Power Systems America: SCH200K-T-US-480 {480V}**](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-sch200k-t-us-480-480v/) Chint Power Systems America | 200,000 W | -48910 W | 480.0 V | 1300.0 V | 97.72% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for DYNAPOWER COMPANY LLC: MPS-250 {480V}?

Check DYNAPOWER COMPANY LLC: MPS-250 {480V} (248,910 W AC, 400 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 600 V DC on DYNAPOWER COMPANY LLC: MPS-250 {480V}.

### DYNAPOWER COMPANY LLC: MPS-250 {480V} Panel & Wire Spec

Size 75 C copper conductors at parallel Cu feeders on a 400 A OCPD breaker (299.4 A continuous).

### Alternative Inverter Comparison

Compare efficiency (95.24%) and MPPT window (350-600 V) directly against EPC Power Corp: 50-100122 {480V} (250,190 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for DYNAPOWER COMPANY LLC: MPS-250 {480V} by DYNAPOWER COMPANY LLC covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.

### What breaker and wire size does DYNAPOWER COMPANY LLC: MPS-250 {480V} require?

At 248,910 W continuous AC (480 V, 3-phase), continuous current is 299.4 A; 125% NEC 690.8/705.12 sizing requires a 400 A breaker and parallel Cu feeders (75 C) wire.

### What commercial switchgear or feeder sizing does DYNAPOWER COMPANY LLC: MPS-250 {480V} require?

At 248,910 W AC and 480 V, 3-phase, continuous line current is 299.4 A, requiring a 400 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

### How does DYNAPOWER COMPANY LLC: MPS-250 {480V} compare to EPC Power Corp: 50-100122 {480V}?

DYNAPOWER COMPANY LLC: MPS-250 {480V} delivers 248,910 W AC at 95.24% CEC efficiency with a 600 V DC ceiling, while EPC Power Corp: 50-100122 {480V} outputs 250,190 W at 480 V, 3-phase.

## Related Pages

Explore DYNAPOWER COMPANY LLC hardware, EPC Power Corp: 50-100122 {480V}, utility rates, and NEC 705.12 sizing calculators alongside DYNAPOWER COMPANY LLC: MPS-250 {480V}.

[All DYNAPOWER COMPANY LLC Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/dynapower-company-llc/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From DYNAPOWER COMPANY LLC

- [All DYNAPOWER COMPANY LLC Specs](https://epri-peac.com/solar-equipment/brands/dynapower-company-llc/)
- [DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {690V}](https://epri-peac.com/solar-equipment/inverters/dynapower-company-llc/dynapower-company-llc-cps-2500-gen5-690v/)
- [DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {600V}](https://epri-peac.com/solar-equipment/inverters/dynapower-company-llc/dynapower-company-llc-cps-1500-gen4-600v/)
- [DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V}](https://epri-peac.com/solar-equipment/inverters/dynapower-company-llc/dynapower-company-llc-cps-2500-gen5-415v/)
- [DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {800V}](https://epri-peac.com/solar-equipment/inverters/dynapower-company-llc/dynapower-company-llc-cps-1250-gen5-800v/)
- [DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V}](https://epri-peac.com/solar-equipment/inverters/dynapower-company-llc/dynapower-company-llc-cps-1500-gen4-480v/)