title: "DYNAPOWER COMPANY LLC: CPS-1500 Inverter (1,199,640W)"
url: https://epri-peac.com/solar-equipment/inverters/dynapower-company-llc/dynapower-company-llc-cps-1500-gen4-480v/
description: "CEC specs for DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V}: 1,199,640W AC, 480V, 1850A OCPD, and NEC 705.12 checks. Source-verified US engineering data."
---

CEC Grid-Support Inverter

# DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} — CEC Inverter Specifications

Manufacturer: [**DYNAPOWER COMPANY LLC**](https://epri-peac.com/solar-equipment/brands/dynapower-company-llc/) Registry: **CEC Verified Engineering Specification**

DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} outputs 1,199,640 W AC at 480 V, 3-phase (1443.0 A continuous, 1,850 A OCPD), ranking #1,865 of 2,343 CEC inverters at 96.13% efficiency with a 740-1,500 V MPPT window and 1,500 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 1,199,640 W

- **AC Voltage** : 480 V, 3-phase

- **Min PV Breaker** : 1,850 A (parallel Cu feeders)

- **CEC Efficiency** : 96.13%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} Compare Against Peer CEC Listings?

How DYNAPOWER COMPANY LLC DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} compares on 96.13% efficiency, MPPT span, and 120% busbar interconnection.

With a 740-1,500 V MPPT tracking band and 1,500 V DC ceiling, DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} handles 1,199,640 W continuous AC (1,149,640 W above the 50,000 W 480 V median). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap. Installers comparing DYNAPOWER COMPANY LLC against Delta Electronics: EPCS-1200US {480V} (1,216,710 W) should verify whether listed since 2024-03-21 grid-support firmware meets local IEEE 1547 utility rules.

## Where Does DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} Fall Across Listed CEC Models?

Position of DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} (1,199,640 W AC) relative to the 7,680 W CEC median inverter.

## What Dataset Percentiles Define DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V}?

Percentile placement of DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} across AC power class, conversion efficiency, and backfeed breaker size.

## What Do the Dataset Ranks Show for DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V}?

Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V}.

Eff #1,865 / 2,343

### 96.13% CEC Weighted Efficiency

-1.89 pts vs the 98.02% 480 V median; overall power rank #150 (1,199,640 W, top 6.4%; higher than 93.6% of peers).

NEC 705.12 Check

### 1,850 A Required Backfeed OCPD

125% x 1443.0 A = 1803.8 A -> 1,850 A standard OCPD using parallel Cu feeders (75 C).

MPPT Window

### 740 V - 1,500 V (Max 1,500 V DC)

Tracking span of 760.0 V; listed since 2024-03-21 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 1199640.0W / 480 V 3-phase -> 1443.0 A | Breaker >= 1.25 * 1443.0 = 1803.8 A -> 1,850 A

CEC Inverters.csv for DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V}: Paco=1199640.0 W, Vac=480 V, Vdcmax=1500.0 V, Eff=96.13%.

**Result:** Min 1,850 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (480V): Supply-Side Tap (705.11) / Dedicated Switchboard.

## What Are the Published CEC Specifications for DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V}?

Official California Energy Commission electrical test parameters, AC voltage, and DC limits for DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V}.

Official California Energy Commission (NREL SAM) test parameters for DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 1,199,640 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 1,500 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 740 V - 1,500 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 1247.94 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 96.13% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2024-03-21 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} (480 V, 3-phase)?

Check whether DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} (1,850 A breaker) fits without main breaker derate or supply-side taps.

Evaluates DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} (1850 A required OCPD at 480 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (480V)** | 40 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (480V)** | 80 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (480V)** | 120 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (480V)** | 160 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (480V)** | 240 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |

## Which CEC PV Module Strings Pair With DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V}?

Verified cold-weather (-10 C) series module counts matched to DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V}'s 1,500 V DC ceiling.

Sampled CEC PV modules aligned within 740.0-1500.0 V MPPT and 1500.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 18 to 26 panels | 15.34 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 23 to 35 panels | 15.4 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 22 to 33 panels | 14.03 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 26 to 36 panels | 7.2 kW |

## Which Competing Grid-Support Inverters Compare to DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V}?

Alternative CEC inverters comparable to DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V}, including Delta Electronics: EPCS-1200US {480V} (1,216,710 W) at 480 V, 3-phase.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Delta Electronics: EPCS-1200US {480V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-epcs-1200us-480v/) Delta Electronics | 1,216,710 W | +17070 W | 480.0 V | 1500.0 V | 97.82% |
| [**EPC Power Corp: 50-100181 {480V}**](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100181-480v/) EPC Power Corp | 1,044,200 W | -155440 W | 480.0 V | 1500.0 V | 97.49% |
| [**EPC Power Corp: 50-100100 {480V}**](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-100100-480v/) EPC Power Corp | 1,036,840 W | -162800 W | 480.0 V | 1250.0 V | 95.42% |
| [**Delta Electronics: DWE2100-US {480V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-dwe2100-us-480v/) Delta Electronics | 1,887,740 W | +688100 W | 480.0 V | 1200.0 V | 96.67% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V}?

Check DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} (1,199,640 W AC, 1,850 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,500 V DC on DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V}.

### DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} Panel & Wire Spec

Size 75 C copper conductors at parallel Cu feeders on a 1,850 A OCPD breaker (1443.0 A continuous).

### Alternative Inverter Comparison

Compare efficiency (96.13%) and MPPT window (740-1,500 V) directly against Delta Electronics: EPCS-1200US {480V} (1,216,710 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} by DYNAPOWER COMPANY LLC covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.

### What breaker and wire size does DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} require?

At 1,199,640 W continuous AC (480 V, 3-phase), continuous current is 1443.0 A; 125% NEC 690.8/705.12 sizing requires a 1,850 A breaker and parallel Cu feeders (75 C) wire.

### What commercial switchgear or feeder sizing does DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} require?

At 1,199,640 W AC and 480 V, 3-phase, continuous line current is 1443.0 A, requiring a 1,850 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

### How does DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} compare to Delta Electronics: EPCS-1200US {480V}?

DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} delivers 1,199,640 W AC at 96.13% CEC efficiency with a 1,500 V DC ceiling, while Delta Electronics: EPCS-1200US {480V} outputs 1,216,710 W at 480 V, 3-phase.

## Related Pages

Explore DYNAPOWER COMPANY LLC hardware, Delta Electronics: EPCS-1200US {480V}, utility rates, and NEC 705.12 sizing calculators alongside DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V}.

[All DYNAPOWER COMPANY LLC Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/dynapower-company-llc/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From DYNAPOWER COMPANY LLC

- [All DYNAPOWER COMPANY LLC Specs](https://epri-peac.com/solar-equipment/brands/dynapower-company-llc/)
- [DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {690V}](https://epri-peac.com/solar-equipment/inverters/dynapower-company-llc/dynapower-company-llc-cps-2500-gen5-690v/)
- [DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {600V}](https://epri-peac.com/solar-equipment/inverters/dynapower-company-llc/dynapower-company-llc-cps-1500-gen4-600v/)
- [DYNAPOWER COMPANY LLC: CPS-2500 Gen5 {415V}](https://epri-peac.com/solar-equipment/inverters/dynapower-company-llc/dynapower-company-llc-cps-2500-gen5-415v/)
- [DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {800V}](https://epri-peac.com/solar-equipment/inverters/dynapower-company-llc/dynapower-company-llc-cps-1250-gen5-800v/)
- [DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {690V}](https://epri-peac.com/solar-equipment/inverters/dynapower-company-llc/dynapower-company-llc-cps-1250-gen5-690v/)