title: "CSI Solar Co Ltd: CSI-125KTL-GS-E Inverter (125,000W)"
url: https://epri-peac.com/solar-equipment/inverters/csi-solar-co-ltd/csi-solar-co-ltd-csi-125ktl-gs-e-600v/
description: "CEC specs for CSI Solar Co Ltd: CSI-125KTL-GS-E {600V}: 125,000W AC, 600V, 175A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} — CEC Inverter Specifications

Manufacturer: [**CSI Solar Co Ltd**](https://epri-peac.com/solar-equipment/brands/csi-solar-co-ltd/) Registry: **CEC Verified Engineering Specification**

CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} outputs 125,000 W AC at 600 V, 3-phase (120.3 A continuous, 175 A OCPD), ranking #44 of 2,343 CEC inverters at 98.63% efficiency with a 860-1,250 V MPPT window and 1,250 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 125,000 W

- **AC Voltage** : 600 V, 3-phase

- **Min PV Breaker** : 175 A (2/0 AWG Cu)

- **CEC Efficiency** : 98.63%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} Compare Against Peer CEC Listings?

CEC efficiency rank (#44), 860-1,250 V MPPT tracking, and panel fit for CSI Solar Co Ltd: CSI-125KTL-GS-E {600V}.

Operating at 600 V, 3-phase, CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} converts DC array energy at 98.63% CEC weighted efficiency (top 1.9%; higher than 98.1% of peers) with a 1,250 V max DC input and 133.404 A max input current for NEC 690.7 string safety. Compare this 125,000 W grid-tied PV inverter directly with Chint Power Systems America: CPS SCH125KTL-AIO/US-600 {600V} (125,000 W). Commercial 600 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (600V) or NEC 705.11 supply-side tap.

## Where Does CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} Fall Across Listed CEC Models?

CEC inverter wattage histogram highlighting CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} at 125,000 W continuous AC output. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.

## What Dataset Percentiles Define CSI Solar Co Ltd: CSI-125KTL-GS-E {600V}?

Dataset percentiles comparing CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} against 2,343 certified grid-support inverters nationwide. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

## What Do the Dataset Ranks Show for CSI Solar Co Ltd: CSI-125KTL-GS-E {600V}?

Engineering highlights for CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} covering efficiency, 2/0 AWG Cu feeder, and panel compatibility.

Eff #44 / 2,343

### 98.63% CEC Weighted Efficiency

+0.35 pts vs the 98.28% 600 V median; overall power rank #300 (125,000 W, top 13.4%; higher than 86.6% of peers).

NEC 705.12 Check

### 175 A Required Backfeed OCPD

125% x 120.3 A = 150.4 A -> 175 A standard OCPD using 2/0 AWG Cu (75 C).

MPPT Window

### 860 V - 1,250 V (Max 1,250 V DC)

Tracking span of 390.0 V; listed since 2021-12-01 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 600 V, 3-phase switchgear (200A Bus / 200A Main (600V) to 1,200A Bus / 1,200A Main (600V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 125000.0W / 600 V 3-phase -> 120.3 A | Breaker >= 1.25 * 120.3 = 150.4 A -> 175 A

CEC Inverters.csv for CSI Solar Co Ltd: CSI-125KTL-GS-E {600V}: Paco=125000.0 W, Vac=600 V, Vdcmax=1250.0 V, Eff=98.63%.

**Result:** Min 175 A breaker & 2/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (600V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for CSI Solar Co Ltd: CSI-125KTL-GS-E {600V}?

California Energy Commission Solar Equipment List parameters for CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} (grid-tied PV inverter) interconnection.

Official California Energy Commission (NREL SAM) test parameters for CSI Solar Co Ltd: CSI-125KTL-GS-E {600V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 125,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 600 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 1,250 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 860 V - 1,250 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 133.404 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 98.63% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2021-12-01 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} (600 V, 3-phase)?

Panelboard and switchgear backfeed allowances for CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} (175 A OCPD). Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.

Evaluates CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} (175 A required OCPD at 600 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (600V)** | 40 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (600V)** | 80 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (600V)** | 120 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (600V)** | 160 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (600V)** | 240 A | 175 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With CSI Solar Co Ltd: CSI-125KTL-GS-E {600V}?

Representative PV panel pairings verified under NEC 690.7 cold Voc for CSI Solar Co Ltd: CSI-125KTL-GS-E {600V}. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Sampled CEC PV modules aligned within 860.0-1250.0 V MPPT and 1250.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 21 to 22 panels | 12.98 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 26 to 29 panels | 12.76 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 25 to 27 panels | 11.47 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 30 panels (fixed) | 6.0 kW |

## Which Competing Grid-Support Inverters Compare to CSI Solar Co Ltd: CSI-125KTL-GS-E {600V}?

Four alternative CEC inverters matched to CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} (125,000 W AC), led by Chint Power Systems America: CPS SCH125KTL-AIO/US-600 {600V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Chint Power Systems America: CPS SCH125KTL-AIO/US-600 {600V}**](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-sch125ktl-aio-us-600-600v/) Chint Power Systems America | 125,000 W | Tie (0 W) | 600.0 V | 1300.0 V | 98.2% |
| [**Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V}**](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-sch125ktl-do-us-600-600v/) Chint Power Systems America | 125,000 W | Tie (0 W) | 600.0 V | 1300.0 V | 98.21% |
| [**Ginlong Technologies Co Ltd: Solis-125K-EHV-5G {600V}**](https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-solis-125k-ehv-5g-600v/) Ginlong Technologies Co Ltd | 125,000 W | Tie (0 W) | 600.0 V | 1250.0 V | 98.63% |
| [**Schneider Electric USA Inc: Conext CL125 {600V}**](https://epri-peac.com/solar-equipment/inverters/schneider-electric-usa-inc/schneider-electric-usa-inc-conext-cl125-600v/) Schneider Electric USA Inc | 125,000 W | Tie (0 W) | 600.0 V | 1200.0 V | 98.1% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for CSI Solar Co Ltd: CSI-125KTL-GS-E {600V}?

Check CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} (125,000 W AC, 175 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 600 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (600V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,250 V DC on CSI Solar Co Ltd: CSI-125KTL-GS-E {600V}.

### CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} Panel & Wire Spec

Size 75 C copper conductors at 2/0 AWG Cu on a 175 A OCPD breaker (120.3 A continuous).

### Alternative Inverter Comparison

Compare efficiency (98.63%) and MPPT window (860-1,250 V) directly against Chint Power Systems America: CPS SCH125KTL-AIO/US-600 {600V} (125,000 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} by CSI Solar Co Ltd covering breaker sizing, MPPT limits, and 600 V, 3-phase interconnection.

### What breaker and wire size does CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} require?

At 125,000 W continuous AC (600 V, 3-phase), continuous current is 120.3 A; 125% NEC 690.8/705.12 sizing requires a 175 A breaker and 2/0 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} require?

At 125,000 W AC and 600 V, 3-phase, continuous line current is 120.3 A, requiring a 175 A OCPD and 1,200A Bus / 1,200A Main (600V) or NEC 705.11 interconnection.

### How does CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} compare to Chint Power Systems America: CPS SCH125KTL-AIO/US-600 {600V}?

CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} delivers 125,000 W AC at 98.63% CEC efficiency with a 1,250 V DC ceiling, while Chint Power Systems America: CPS SCH125KTL-AIO/US-600 {600V} outputs 125,000 W at 600 V, 3-phase.

## Related Pages

Explore CSI Solar Co Ltd hardware, Chint Power Systems America: CPS SCH125KTL-AIO/US-600 {600V}, utility rates, and NEC 705.12 sizing calculators alongside CSI Solar Co Ltd: CSI-125KTL-GS-E {600V}.

[All CSI Solar Co Ltd Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/csi-solar-co-ltd/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From CSI Solar Co Ltd

- [All CSI Solar Co Ltd Specs](https://epri-peac.com/solar-equipment/brands/csi-solar-co-ltd/)
- [CSI Solar Co Ltd: CSI-255K-T800GL02-U {800V}](https://epri-peac.com/solar-equipment/inverters/csi-solar-co-ltd/csi-solar-co-ltd-csi-255k-t800gl02-u-800v/)
- [CSI Solar Co Ltd: CSI-255K-T800GL03-U {800V}](https://epri-peac.com/solar-equipment/inverters/csi-solar-co-ltd/csi-solar-co-ltd-csi-255k-t800gl03-u-800v/)
- [CSI Solar Co Ltd: CSEC-215K-T6901A-U {690V}](https://epri-peac.com/solar-equipment/inverters/csi-solar-co-ltd/csi-solar-co-ltd-csec-215k-t6901a-u-690v/)
- [CSI Solar Co Ltd: CSEC-200K-T6901A-U {690V}](https://epri-peac.com/solar-equipment/inverters/csi-solar-co-ltd/csi-solar-co-ltd-csec-200k-t6901a-u-690v/)
- [CSI Solar Co Ltd: CSI-185K-T600GL02-U {600V}](https://epri-peac.com/solar-equipment/inverters/csi-solar-co-ltd/csi-solar-co-ltd-csi-185k-t600gl02-u-600v/)