title: "Chint Power Systems America Inverter (50,000W)"
url: https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-sca50k-t-us-208-208v/
description: "CEC specs for Chint Power Systems America: SCA50K-T-US-208 {208V}: 50,000W AC, 208V, 175A OCPD, and NEC 705.12 checks. Source-verified US engineering data."
---

CEC Grid-Support Inverter

# Chint Power Systems America: SCA50K-T-US-208 {208V} — CEC Inverter Specifications

Manufacturer: [**Chint Power Systems America**](https://epri-peac.com/solar-equipment/brands/chint-power-systems-america/) Registry: **CEC Verified Engineering Specification**

Chint Power Systems America: SCA50K-T-US-208 {208V} outputs 50,000 W AC at 208 V, 3-phase (138.8 A continuous, 175 A OCPD), ranking #2,021 of 2,343 CEC inverters at 95.93% efficiency with a 200-700 V MPPT window and 700 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 50,000 W

- **AC Voltage** : 208 V, 3-phase

- **Min PV Breaker** : 175 A (2/0 AWG Cu)

- **CEC Efficiency** : 95.93%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Chint Power Systems America: SCA50K-T-US-208 {208V} Compare Against Peer CEC Listings?

Breaker sizing (175 A), 2/0 AWG Cu wire rules, and DC input limits for Chint Power Systems America: SCA50K-T-US-208 {208V}.

For NEC 705.12 solar interconnection, Chint Power Systems America: SCA50K-T-US-208 {208V} outputs 138.8 A continuous AC at 208 V, 3-phase and needs a 175 A backfeed breaker on 2/0 AWG Cu (75 C). Commercial 208 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap. Conversion efficiency scores 95.93% (#2,021 of 2,343, -0.89 pts vs overall CEC median).

## Where Does Chint Power Systems America: SCA50K-T-US-208 {208V} Fall Across Listed CEC Models?

Output power comparison showing where Chint Power Systems America: SCA50K-T-US-208 {208V} sits among all 2,343 CEC-listed grid-support inverters.

## What Dataset Percentiles Define Chint Power Systems America: SCA50K-T-US-208 {208V}?

Relative ranking of Chint Power Systems America: SCA50K-T-US-208 {208V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.

## What Do the Dataset Ranks Show for Chint Power Systems America: SCA50K-T-US-208 {208V}?

Snapshot of Chint Power Systems America: SCA50K-T-US-208 {208V} efficiency rank (#2,021), OCPD breaker size, MPPT span, and busbar verdict.

Eff #2,021 / 2,343

### 95.93% CEC Weighted Efficiency

-0.48 pts vs the 96.41% 208 V median; overall power rank #438 (50,000 W, top 19.3%; higher than 80.7% of peers).

NEC 705.12 Check

### 175 A Required Backfeed OCPD

125% x 138.8 A = 173.5 A -> 175 A standard OCPD using 2/0 AWG Cu (75 C).

MPPT Window

### 200 V - 700 V (Max 700 V DC)

Tracking span of 500.0 V; listed since 2026-04-21 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 208 V, 3-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 50000.0W / 208 V 3-phase -> 138.8 A | Breaker >= 1.25 * 138.8 = 173.5 A -> 175 A

CEC Inverters.csv for Chint Power Systems America: SCA50K-T-US-208 {208V}: Paco=50000.0 W, Vac=208 V, Vdcmax=700.0 V, Eff=95.93%.

**Result:** Min 175 A breaker & 2/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for Chint Power Systems America: SCA50K-T-US-208 {208V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Chint Power Systems America: SCA50K-T-US-208 {208V}.

Official California Energy Commission (NREL SAM) test parameters for Chint Power Systems America: SCA50K-T-US-208 {208V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 50,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 208 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 700 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 200 V - 700 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 137.166 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 95.93% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2026-04-21 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to Chint Power Systems America: SCA50K-T-US-208 {208V} (208 V, 3-phase)?

NEC 705.12(B)(3)(2) backfeed compliance table for Chint Power Systems America: SCA50K-T-US-208 {208V} at 208 V, 3-phase.

Evaluates Chint Power Systems America: SCA50K-T-US-208 {208V} (175 A required OCPD at 208 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (208V)** | 40 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (208V)** | 80 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (208V)** | 120 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (208V)** | 160 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (208V)** | 240 A | 175 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With Chint Power Systems America: SCA50K-T-US-208 {208V}?

Minimum and maximum series solar module strings fitting Chint Power Systems America: SCA50K-T-US-208 {208V} MPPT and 700 V limits.

Sampled CEC PV modules aligned within 200.0-700.0 V MPPT and 700.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 5 to 12 panels | 7.08 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 6 to 16 panels | 7.04 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 6 to 15 panels | 6.38 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 7 to 17 panels | 3.4 kW |

## Which Competing Grid-Support Inverters Compare to Chint Power Systems America: SCA50K-T-US-208 {208V}?

Peer 208 V, 3-phase CEC inverters near 50,000 W AC output such as CSI Solar Co Ltd: CSI-30K-T208GL03-U {208V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**CSI Solar Co Ltd: CSI-30K-T208GL03-U {208V}**](https://epri-peac.com/solar-equipment/inverters/csi-solar-co-ltd/csi-solar-co-ltd-csi-30k-t208gl03-u-208v/) CSI Solar Co Ltd | 29,878 W | -20122 W | 208.0 V | 680.0 V | 96.38% |
| [**EcoFlow Inc: EF-PCS-24 {208V 24kW}**](https://epri-peac.com/solar-equipment/inverters/ecoflow-inc/ecoflow-inc-ef-pcs-24-208v-24kw/) EcoFlow Inc | 24,291 W | -25709 W | 208.0 V | 480.0 V | 96.01% |
| [**EG4 Electronics LLC: IV-16000-HYB-AW-FX-xx {208V}**](https://epri-peac.com/solar-equipment/inverters/eg4-electronics-llc/eg4-electronics-llc-iv-16000-hyb-aw-fx-xx-208v/) EG4 Electronics LLC | 13,899 W | -36101 W | 208.0 V | 440.0 V | 96.46% |
| [**EcoFlow Inc: EF-PCS-24 {208V 115kW}**](https://epri-peac.com/solar-equipment/inverters/ecoflow-inc/ecoflow-inc-ef-pcs-24-208v-115kw/) EcoFlow Inc | 11,444 W | -38556 W | 208.0 V | 480.0 V | 96.52% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for Chint Power Systems America: SCA50K-T-US-208 {208V}?

Check Chint Power Systems America: SCA50K-T-US-208 {208V} (50,000 W AC, 175 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 700 V DC on Chint Power Systems America: SCA50K-T-US-208 {208V}.

### Chint Power Systems America: SCA50K-T-US-208 {208V} Panel & Wire Spec

Size 75 C copper conductors at 2/0 AWG Cu on a 175 A OCPD breaker (138.8 A continuous).

### Alternative Inverter Comparison

Compare efficiency (95.93%) and MPPT window (200-700 V) directly against CSI Solar Co Ltd: CSI-30K-T208GL03-U {208V} (29,878 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Chint Power Systems America: SCA50K-T-US-208 {208V} by Chint Power Systems America covering breaker sizing, MPPT limits, and 208 V, 3-phase interconnection.

### What breaker and wire size does Chint Power Systems America: SCA50K-T-US-208 {208V} require?

At 50,000 W continuous AC (208 V, 3-phase), continuous current is 138.8 A; 125% NEC 690.8/705.12 sizing requires a 175 A breaker and 2/0 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does Chint Power Systems America: SCA50K-T-US-208 {208V} require?

At 50,000 W AC and 208 V, 3-phase, continuous line current is 138.8 A, requiring a 175 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.

### How does Chint Power Systems America: SCA50K-T-US-208 {208V} compare to CSI Solar Co Ltd: CSI-30K-T208GL03-U {208V}?

Chint Power Systems America: SCA50K-T-US-208 {208V} delivers 50,000 W AC at 95.93% CEC efficiency with a 700 V DC ceiling, while CSI Solar Co Ltd: CSI-30K-T208GL03-U {208V} outputs 29,878 W at 208 V, 3-phase.

## Related Pages

Explore Chint Power Systems America hardware, CSI Solar Co Ltd: CSI-30K-T208GL03-U {208V}, utility rates, and NEC 705.12 sizing calculators alongside Chint Power Systems America: SCA50K-T-US-208 {208V}.

[All Chint Power Systems America Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/chint-power-systems-america/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From Chint Power Systems America

- [All Chint Power Systems America Specs](https://epri-peac.com/solar-equipment/brands/chint-power-systems-america/)
- [Chint Power Systems America: CPS SCH350KTL-DO/US-800 {800V}](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-sch350ktl-do-us-800-800v/)
- [Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V}](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-sch320ktl-do-us-800-800v/)
- [Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V}](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-sch275ktl-do-us-800-800v/)
- [Chint Power Systems America: SCH250K-T-US-600 {600V}](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-sch250k-t-us-600-600v/)
- [Chint Power Systems America: CPS ECB200KTL/US-800 {800V}](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-ecb200ktl-us-800-800v/)