title: "Chint Power Systems America Inverter (100,000W)"
url: https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-sca100k-t-us-480-480v/
description: "CEC specs for Chint Power Systems America: SCA100K-T-US-480 {480V}: 100,000W AC, 480V, 175A OCPD, and NEC 705.12 checks. Source-verified US engineering data."
---

CEC Grid-Support Inverter

# Chint Power Systems America: SCA100K-T-US-480 {480V} — CEC Inverter Specifications

Manufacturer: [**Chint Power Systems America**](https://epri-peac.com/solar-equipment/brands/chint-power-systems-america/) Registry: **CEC Verified Engineering Specification**

Chint Power Systems America: SCA100K-T-US-480 {480V} outputs 100,000 W AC at 480 V, 3-phase (120.3 A continuous, 175 A OCPD), ranking #318 of 2,343 CEC inverters at 98.05% efficiency with a 340-850 V MPPT window and 850 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 100,000 W

- **AC Voltage** : 480 V, 3-phase

- **Min PV Breaker** : 175 A (2/0 AWG Cu)

- **CEC Efficiency** : 98.05%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Chint Power Systems America: SCA100K-T-US-480 {480V} Compare Against Peer CEC Listings?

Breaker sizing (175 A), 2/0 AWG Cu wire rules, and DC input limits for Chint Power Systems America: SCA100K-T-US-480 {480V}.

For NEC 705.12 solar interconnection, Chint Power Systems America: SCA100K-T-US-480 {480V} outputs 120.3 A continuous AC at 480 V, 3-phase and needs a 175 A backfeed breaker on 2/0 AWG Cu (75 C). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap. Conversion efficiency scores 98.05% (#318 of 2,343, +1.23 pts vs overall CEC median).

## Where Does Chint Power Systems America: SCA100K-T-US-480 {480V} Fall Across Listed CEC Models?

Output power comparison showing where Chint Power Systems America: SCA100K-T-US-480 {480V} sits among all 2,343 CEC-listed grid-support inverters.

## What Dataset Percentiles Define Chint Power Systems America: SCA100K-T-US-480 {480V}?

Relative ranking of Chint Power Systems America: SCA100K-T-US-480 {480V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.

## What Do the Dataset Ranks Show for Chint Power Systems America: SCA100K-T-US-480 {480V}?

Snapshot of Chint Power Systems America: SCA100K-T-US-480 {480V} efficiency rank (#318), OCPD breaker size, MPPT span, and busbar verdict.

Eff #318 / 2,343

### 98.05% CEC Weighted Efficiency

+0.03 pts vs the 98.02% 480 V median; overall power rank #332 (100,000 W, top 14.5%; higher than 85.5% of peers).

NEC 705.12 Check

### 175 A Required Backfeed OCPD

125% x 120.3 A = 150.4 A -> 175 A standard OCPD using 2/0 AWG Cu (75 C).

MPPT Window

### 340 V - 850 V (Max 850 V DC)

Tracking span of 510.0 V; active in CEC directory (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 100000.0W / 480 V 3-phase -> 120.3 A | Breaker >= 1.25 * 120.3 = 150.4 A -> 175 A

CEC Inverters.csv for Chint Power Systems America: SCA100K-T-US-480 {480V}: Paco=100000.0 W, Vac=480 V, Vdcmax=850.0 V, Eff=98.05%.

**Result:** Min 175 A breaker & 2/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for Chint Power Systems America: SCA100K-T-US-480 {480V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Chint Power Systems America: SCA100K-T-US-480 {480V}.

Official California Energy Commission (NREL SAM) test parameters for Chint Power Systems America: SCA100K-T-US-480 {480V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 100,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 850 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 340 V - 850 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 141.649 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 98.05% | Calculated AC/DC conversion ratio from CEC test protocol |
| **Inverter Topology** | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |

## What Switchgear Limits Apply to Chint Power Systems America: SCA100K-T-US-480 {480V} (480 V, 3-phase)?

NEC 705.12(B)(3)(2) backfeed compliance table for Chint Power Systems America: SCA100K-T-US-480 {480V} at 480 V, 3-phase.

Evaluates Chint Power Systems America: SCA100K-T-US-480 {480V} (175 A required OCPD at 480 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (480V)** | 40 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (480V)** | 80 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (480V)** | 120 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (480V)** | 160 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (480V)** | 240 A | 175 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With Chint Power Systems America: SCA100K-T-US-480 {480V}?

Minimum and maximum series solar module strings fitting Chint Power Systems America: SCA100K-T-US-480 {480V} MPPT and 850 V limits.

Sampled CEC PV modules aligned within 340.0-850.0 V MPPT and 850.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 8 to 15 panels | 8.85 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 11 to 20 panels | 8.8 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 10 to 18 panels | 7.65 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 12 to 20 panels | 4.0 kW |

## Which Competing Grid-Support Inverters Compare to Chint Power Systems America: SCA100K-T-US-480 {480V}?

Peer 480 V, 3-phase CEC inverters near 100,000 W AC output such as CSI Solar Co Ltd: CSI-100K-T480GL02-U {480V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**CSI Solar Co Ltd: CSI-100K-T480GL02-U {480V}**](https://epri-peac.com/solar-equipment/inverters/csi-solar-co-ltd/csi-solar-co-ltd-csi-100k-t480gl02-u-480v/) CSI Solar Co Ltd | 100,000 W | Tie (0 W) | 480.0 V | 850.0 V | 98.25% |
| [**Ginlong Technologies Co Ltd: Solis-100K-5G-US {480V}**](https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-solis-100k-5g-us-480v/) Ginlong Technologies Co Ltd | 100,000 W | Tie (0 W) | 480.0 V | 850.0 V | 98.25% |
| [**Delta Electronics: M100U_280 {480V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-m100u-280-480v/) Delta Electronics | 99,975 W | -25 W | 480.0 V | 840.0 V | 97.95% |
| [**CSI Solar Co Ltd: CSI-100K-T480GL03-U {480V}**](https://epri-peac.com/solar-equipment/inverters/csi-solar-co-ltd/csi-solar-co-ltd-csi-100k-t480gl03-u-480v/) CSI Solar Co Ltd | 99,368 W | -632 W | 480.0 V | 850.0 V | 97.92% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for Chint Power Systems America: SCA100K-T-US-480 {480V}?

Check Chint Power Systems America: SCA100K-T-US-480 {480V} (100,000 W AC, 175 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 850 V DC on Chint Power Systems America: SCA100K-T-US-480 {480V}.

### Chint Power Systems America: SCA100K-T-US-480 {480V} Panel & Wire Spec

Size 75 C copper conductors at 2/0 AWG Cu on a 175 A OCPD breaker (120.3 A continuous).

### Alternative Inverter Comparison

Compare efficiency (98.05%) and MPPT window (340-850 V) directly against CSI Solar Co Ltd: CSI-100K-T480GL02-U {480V} (100,000 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Chint Power Systems America: SCA100K-T-US-480 {480V} by Chint Power Systems America covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.

### What breaker and wire size does Chint Power Systems America: SCA100K-T-US-480 {480V} require?

At 100,000 W continuous AC (480 V, 3-phase), continuous current is 120.3 A; 125% NEC 690.8/705.12 sizing requires a 175 A breaker and 2/0 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does Chint Power Systems America: SCA100K-T-US-480 {480V} require?

At 100,000 W AC and 480 V, 3-phase, continuous line current is 120.3 A, requiring a 175 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

### How does Chint Power Systems America: SCA100K-T-US-480 {480V} compare to CSI Solar Co Ltd: CSI-100K-T480GL02-U {480V}?

Chint Power Systems America: SCA100K-T-US-480 {480V} delivers 100,000 W AC at 98.05% CEC efficiency with a 850 V DC ceiling, while CSI Solar Co Ltd: CSI-100K-T480GL02-U {480V} outputs 100,000 W at 480 V, 3-phase.

## Related Pages

Explore Chint Power Systems America hardware, CSI Solar Co Ltd: CSI-100K-T480GL02-U {480V}, utility rates, and NEC 705.12 sizing calculators alongside Chint Power Systems America: SCA100K-T-US-480 {480V}.

[All Chint Power Systems America Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/chint-power-systems-america/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From Chint Power Systems America

- [All Chint Power Systems America Specs](https://epri-peac.com/solar-equipment/brands/chint-power-systems-america/)
- [Chint Power Systems America: CPS SCH350KTL-DO/US-800 {800V}](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-sch350ktl-do-us-800-800v/)
- [Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V}](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-sch320ktl-do-us-800-800v/)
- [Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V}](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-sch275ktl-do-us-800-800v/)
- [Chint Power Systems America: SCH250K-T-US-600 {600V}](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-sch250k-t-us-600-600v/)
- [Chint Power Systems America: CPS ECB200KTL/US-800 {800V}](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-ecb200ktl-us-800-800v/)