title: "Chint Power Systems America: CPS Inverter (275,000W)"
url: https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-sch275ktl-do-us-800-800v/
description: "CEC specs for Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V}: 275,000W AC, 800V, 250A OCPD, and NEC 705.12 checks."
---

CEC Grid-Support Inverter

# Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V} — CEC Inverter Specifications

Manufacturer: [**Chint Power Systems America**](https://epri-peac.com/solar-equipment/brands/chint-power-systems-america/) Registry: **CEC Verified Engineering Specification**

Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V} outputs 275,000 W AC at 800 V, 3-phase (198.5 A continuous, 250 A OCPD), ranking #77 of 2,343 CEC inverters at 98.5% efficiency with a 900-1,300 V MPPT window and 1,300 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 275,000 W

- **AC Voltage** : 800 V, 3-phase

- **Min PV Breaker** : 250 A (parallel Cu feeders)

- **CEC Efficiency** : 98.5%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V} Compare Against Peer CEC Listings?

NEC 705.12 breaker requirements, efficiency placement, and 800 V, 3-phase grid-support overview for Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V}.

Ranking #217 of 2,343 CEC inverters (top 9.3%; higher than 90.7% of peers), Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V} is a grid-tied PV inverter delivering 275,000 W continuous AC at 800 V, 3-phase (198.5 A continuous). Commercial 800 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (800V) or NEC 705.11 supply-side tap. Weighted CEC efficiency reaches 98.5% (+0.20 pts vs the 98.3% 800 V median) against peers like CSI Solar Co Ltd: CSI-255K-T800GL02-U {800V} (255,013 W).

## Where Does Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V} Fall Across Listed CEC Models?

Marks Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V} (275,000 W AC) across the California Energy Commission inverter AC capacity distribution.

## What Dataset Percentiles Define Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V}?

Benchmarks Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V} continuous AC output, 98.5% CEC weighted efficiency, and 250 A OCPD breaker demand.

## What Do the Dataset Ranks Show for Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V}?

Four key NEC 705.12 and California Energy Commission metrics defining Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V} by Chint Power Systems America.

Eff #77 / 2,343

### 98.5% CEC Weighted Efficiency

+0.20 pts vs the 98.3% 800 V median; overall power rank #217 (275,000 W, top 9.3%; higher than 90.7% of peers).

NEC 705.12 Check

### 250 A Required Backfeed OCPD

125% x 198.5 A = 248.1 A -> 250 A standard OCPD using parallel Cu feeders (75 C).

MPPT Window

### 900 V - 1,300 V (Max 1,300 V DC)

Tracking span of 400.0 V; listed since 2022-09-12 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 800 V, 3-phase switchgear (200A Bus / 200A Main (800V) to 1,200A Bus / 1,200A Main (800V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 275000.0W / 800 V 3-phase -> 198.5 A | Breaker >= 1.25 * 198.5 = 248.1 A -> 250 A

CEC Inverters.csv for Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V}: Paco=275000.0 W, Vac=800 V, Vdcmax=1300.0 V, Eff=98.5%.

**Result:** Min 250 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (800V): Supply-Side Tap (705.11) / Dedicated Switchboard.

## What Are the Published CEC Specifications for Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V}?

Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V}.

Official California Energy Commission (NREL SAM) test parameters for Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 275,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 800 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 1,300 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 900 V - 1,300 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 234.61 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 98.5% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2022-09-12 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V} (800 V, 3-phase)?

Evaluates Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V} (250 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.

Evaluates Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V} (250 A required OCPD at 800 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (800V)** | 40 A | 250 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (800V)** | 80 A | 250 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (800V)** | 120 A | 250 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (800V)** | 160 A | 250 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (800V)** | 240 A | 250 A | Supply-Side Tap (705.11) / Dedicated Switchboard |

## Which CEC PV Module Strings Pair With Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V}?

Sample PV string lengths aligned within 900-1,300 V MPPT and 1,300 V DC max at -10 C. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

Sampled CEC PV modules aligned within 900.0-1300.0 V MPPT and 1300.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 21 to 23 panels | 13.57 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 27 to 30 panels | 13.2 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 27 to 29 panels | 12.32 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 32 panels (fixed) | 6.4 kW |

## Which Competing Grid-Support Inverters Compare to Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V}?

Competing CEC grid-support inverters near 275,000 W AC and 800 V, 3-phase, led by CSI Solar Co Ltd: CSI-255K-T800GL02-U {800V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**CSI Solar Co Ltd: CSI-255K-T800GL02-U {800V}**](https://epri-peac.com/solar-equipment/inverters/csi-solar-co-ltd/csi-solar-co-ltd-csi-255k-t800gl02-u-800v/) CSI Solar Co Ltd | 255,013 W | -19987 W | 800.0 V | 1300.0 V | 98.34% |
| [**CSI Solar Co Ltd: CSI-255K-T800GL03-U {800V}**](https://epri-peac.com/solar-equipment/inverters/csi-solar-co-ltd/csi-solar-co-ltd-csi-255k-t800gl03-u-800v/) CSI Solar Co Ltd | 255,013 W | -19987 W | 800.0 V | 1300.0 V | 98.34% |
| [**Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US {800V}**](https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-solis-255k-ehv-5g-us-800v/) Ginlong Technologies Co Ltd | 255,013 W | -19987 W | 800.0 V | 1300.0 V | 98.34% |
| [**Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}**](https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-solis-255k-ehv-5g-us-plus-800v/) Ginlong Technologies Co Ltd | 238,706 W | -36294 W | 800.0 V | 1300.0 V | 98.26% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V}?

Check Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V} (275,000 W AC, 250 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 800 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (800V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,300 V DC on Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V}.

### Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V} Panel & Wire Spec

Size 75 C copper conductors at parallel Cu feeders on a 250 A OCPD breaker (198.5 A continuous).

### Alternative Inverter Comparison

Compare efficiency (98.5%) and MPPT window (900-1,300 V) directly against CSI Solar Co Ltd: CSI-255K-T800GL02-U {800V} (255,013 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V} by Chint Power Systems America covering breaker sizing, MPPT limits, and 800 V, 3-phase interconnection.

### What breaker and wire size does Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V} require?

At 275,000 W continuous AC (800 V, 3-phase), continuous current is 198.5 A; 125% NEC 690.8/705.12 sizing requires a 250 A breaker and parallel Cu feeders (75 C) wire.

### What commercial switchgear or feeder sizing does Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V} require?

At 275,000 W AC and 800 V, 3-phase, continuous line current is 198.5 A, requiring a 250 A OCPD and 1,200A Bus / 1,200A Main (800V) or NEC 705.11 interconnection.

### How does Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V} compare to CSI Solar Co Ltd: CSI-255K-T800GL02-U {800V}?

Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V} delivers 275,000 W AC at 98.5% CEC efficiency with a 1,300 V DC ceiling, while CSI Solar Co Ltd: CSI-255K-T800GL02-U {800V} outputs 255,013 W at 800 V, 3-phase.

## Related Pages

Explore Chint Power Systems America hardware, CSI Solar Co Ltd: CSI-255K-T800GL02-U {800V}, utility rates, and NEC 705.12 sizing calculators alongside Chint Power Systems America: CPS SCH275KTL-DO/US-800 {800V}.

[All Chint Power Systems America Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/chint-power-systems-america/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From Chint Power Systems America

- [All Chint Power Systems America Specs](https://epri-peac.com/solar-equipment/brands/chint-power-systems-america/)
- [Chint Power Systems America: CPS SCH350KTL-DO/US-800 {800V}](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-sch350ktl-do-us-800-800v/)
- [Chint Power Systems America: CPS SCH320KTL-DO/US-800 {800V}](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-sch320ktl-do-us-800-800v/)
- [Chint Power Systems America: SCH250K-T-US-600 {600V}](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-sch250k-t-us-600-600v/)
- [Chint Power Systems America: CPS ECB200KTL/US-800 {800V}](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-ecb200ktl-us-800-800v/)
- [Chint Power Systems America: SCH200K-T-US-480 {480V}](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-sch200k-t-us-480-480v/)