CEC Grid-Support Inverter

# Canadian Solar Inc: CSI-36KTL-GS-FL {480V} — CEC Inverter Specifications

Manufacturer: [**Canadian Solar Inc**](https://epri-peac.com/solar-equipment/brands/canadian-solar-inc/) Registry: **CEC Verified Engineering Specification**

Canadian Solar Inc: CSI-36KTL-GS-FL {480V} outputs 36,000 W AC at 480 V, 3-phase (43.3 A continuous, 60 A OCPD), ranking #318 of 2,343 CEC inverters at 98.05% efficiency with a 580-780 V MPPT window and 780 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 36,000 W

- **AC Voltage** : 480 V, 3-phase

- **Min PV Breaker** : 60 A (6 AWG Cu)

- **CEC Efficiency** : 98.05%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Canadian Solar Inc: CSI-36KTL-GS-FL {480V} Compare Against Peer CEC Listings?

Breaker sizing (60 A), 6 AWG Cu wire rules, and DC input limits for Canadian Solar Inc: CSI-36KTL-GS-FL {480V}.

Classified as a grid-tied PV inverter (listed since 2019-11-15), Canadian Solar Inc: CSI-36KTL-GS-FL {480V} requires 54.1 A design capacity -> 60 A breaker using 6 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 98.05% (+1.23 pts vs overall CEC median) across 2,343 CEC models, while commercial 480 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (480v) or nec 705.11 supply-side tap.

## Where Does Canadian Solar Inc: CSI-36KTL-GS-FL {480V} Fall Across Listed CEC Models?

Output power comparison showing where Canadian Solar Inc: CSI-36KTL-GS-FL {480V} sits among all 2,343 CEC-listed grid-support inverters. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.

## What Dataset Percentiles Define Canadian Solar Inc: CSI-36KTL-GS-FL {480V}?

Relative ranking of Canadian Solar Inc: CSI-36KTL-GS-FL {480V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.

## What Do the Dataset Ranks Show for Canadian Solar Inc: CSI-36KTL-GS-FL {480V}?

Snapshot of Canadian Solar Inc: CSI-36KTL-GS-FL {480V} efficiency rank (#318), OCPD breaker size, MPPT span, and busbar verdict.

Eff #318 / 2,343

### 98.05% CEC Weighted Efficiency

+0.03 pts vs the 98.02% 480 V median; overall power rank #510 (36,000 W, top 22.2%; higher than 77.8% of peers).

NEC 705.12 Check

### 60 A Required Backfeed OCPD

125% x 43.3 A = 54.1 A -> 60 A standard OCPD using 6 AWG Cu (75 C).

MPPT Window

### 580 V - 780 V (Max 780 V DC)

Tracking span of 200.0 V; listed since 2019-11-15 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### PASS (120% Commercial Busbar)

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 36000.0W / 480 V 3-phase -> 43.3 A | Breaker >= 1.25 * 43.3 = 54.1 A -> 60 A

CEC Inverters.csv for Canadian Solar Inc: CSI-36KTL-GS-FL {480V}: Paco=36000.0 W, Vac=480 V, Vdcmax=780.0 V, Eff=98.05%.

**Result:** Min 60 A breaker & 6 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for Canadian Solar Inc: CSI-36KTL-GS-FL {480V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Canadian Solar Inc: CSI-36KTL-GS-FL {480V}. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Official California Energy Commission (NREL SAM) test parameters for Canadian Solar Inc: CSI-36KTL-GS-FL {480V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 36,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 780 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 580 V - 780 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 56.4834 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 98.05% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2019-11-15 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to Canadian Solar Inc: CSI-36KTL-GS-FL {480V} (480 V, 3-phase)?

NEC 705.12(B)(3)(2) backfeed compliance table for Canadian Solar Inc: CSI-36KTL-GS-FL {480V} at 480 V, 3-phase.

Evaluates Canadian Solar Inc: CSI-36KTL-GS-FL {480V} (60 A required OCPD at 480 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (480V)** | 40 A | 60 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (480V)** | 80 A | 60 A | PASS (120% Commercial Busbar) |
| **600A Bus / 600A Main (480V)** | 120 A | 60 A | PASS (120% Commercial Busbar) |
| **800A Bus / 800A Main (480V)** | 160 A | 60 A | PASS (120% Commercial Busbar) |
| **1,200A Bus / 1,200A Main (480V)** | 240 A | 60 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With Canadian Solar Inc: CSI-36KTL-GS-FL {480V}?

Minimum and maximum series solar module strings fitting Canadian Solar Inc: CSI-36KTL-GS-FL {480V} MPPT and 780 V limits.

Sampled CEC PV modules aligned within 580.0-780.0 V MPPT and 780.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 18 panels (fixed) | 7.92 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 17 panels (fixed) | 7.22 kW |
| [**G-Star Pte Ltd GSN8K66T(H)740WT**](https://epri-peac.com/solar-equipment/modules/g-star-pte-ltd/g-star-pte-ltd-gsn8k66t-h-740wt/) | 740.0 W | 54.38 V | 14 panels (fixed) | 10.36 kW |

## Which Competing Grid-Support Inverters Compare to Canadian Solar Inc: CSI-36KTL-GS-FL {480V}?

Peer 480 V, 3-phase CEC inverters near 36,000 W AC output such as Chint Power Systems America: CPS SCA36KTL-DO/US-480 {480V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Chint Power Systems America: CPS SCA36KTL-DO/US-480 {480V}**](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-sca36ktl-do-us-480-480v/) Chint Power Systems America | 36,000 W | Tie (0 W) | 480.0 V | 850.0 V | 97.62% |
| [**Chint Power Systems America: CPS SCA36KTL-DO/US {480V}**](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-sca36ktl-do-us-480v/) Chint Power Systems America | 36,000 W | Tie (0 W) | 480.0 V | 800.0 V | 98.09% |
| [**CSI Solar Co Ltd: CSI-36KTL-GS-FLB {480V}**](https://epri-peac.com/solar-equipment/inverters/csi-solar-co-ltd/csi-solar-co-ltd-csi-36ktl-gs-flb-480v/) CSI Solar Co Ltd | 36,000 W | Tie (0 W) | 480.0 V | 780.0 V | 98.11% |
| [**CSI Solar Co Ltd: CSI-36K-T480GL01-UB {480V}**](https://epri-peac.com/solar-equipment/inverters/csi-solar-co-ltd/csi-solar-co-ltd-csi-36k-t480gl01-ub-480v/) CSI Solar Co Ltd | 35,925 W | -75 W | 480.0 V | 800.0 V | 98.32% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for Canadian Solar Inc: CSI-36KTL-GS-FL {480V}?

Check Canadian Solar Inc: CSI-36KTL-GS-FL {480V} (36,000 W AC, 60 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 780 V DC on Canadian Solar Inc: CSI-36KTL-GS-FL {480V}.

### Canadian Solar Inc: CSI-36KTL-GS-FL {480V} Panel & Wire Spec

Size 75 C copper conductors at 6 AWG Cu on a 60 A OCPD breaker (43.3 A continuous).

### Alternative Inverter Comparison

Compare efficiency (98.05%) and MPPT window (580-780 V) directly against Chint Power Systems America: CPS SCA36KTL-DO/US-480 {480V} (36,000 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Canadian Solar Inc: CSI-36KTL-GS-FL {480V} by Canadian Solar Inc covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.

### What breaker and wire size does Canadian Solar Inc: CSI-36KTL-GS-FL {480V} require?

At 36,000 W continuous AC (480 V, 3-phase), continuous current is 43.3 A; 125% NEC 690.8/705.12 sizing requires a 60 A breaker and 6 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does Canadian Solar Inc: CSI-36KTL-GS-FL {480V} require?

At 36,000 W AC and 480 V, 3-phase, continuous line current is 43.3 A, requiring a 60 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

### How does Canadian Solar Inc: CSI-36KTL-GS-FL {480V} compare to Chint Power Systems America: CPS SCA36KTL-DO/US-480 {480V}?

Canadian Solar Inc: CSI-36KTL-GS-FL {480V} delivers 36,000 W AC at 98.05% CEC efficiency with a 780 V DC ceiling, while Chint Power Systems America: CPS SCA36KTL-DO/US-480 {480V} outputs 36,000 W at 480 V, 3-phase.

## Related Pages

Explore Canadian Solar Inc hardware, Chint Power Systems America: CPS SCA36KTL-DO/US-480 {480V}, utility rates, and NEC 705.12 sizing calculators alongside Canadian Solar Inc: CSI-36KTL-GS-FL {480V}.

[All Canadian Solar Inc Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/canadian-solar-inc/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From Canadian Solar Inc

- [All Canadian Solar Inc Specs](https://epri-peac.com/solar-equipment/brands/canadian-solar-inc/)
- [Canadian Solar Inc: CSI-66KTL-GS {480V}](https://epri-peac.com/solar-equipment/inverters/canadian-solar-inc/canadian-solar-inc-csi-66ktl-gs-480v/)
- [Canadian Solar Inc: CSI-60KTL-CT {480V}](https://epri-peac.com/solar-equipment/inverters/canadian-solar-inc/canadian-solar-inc-csi-60ktl-ct-480v/)
- [Canadian Solar Inc: CSI-60KTL-GS {480V}](https://epri-peac.com/solar-equipment/inverters/canadian-solar-inc/canadian-solar-inc-csi-60ktl-gs-480v/)
- [Canadian Solar Inc: CSI-50KTL-CT {480V}](https://epri-peac.com/solar-equipment/inverters/canadian-solar-inc/canadian-solar-inc-csi-50ktl-ct-480v/)
- [Canadian Solar Inc: CSI-50KTL-GS {480V}](https://epri-peac.com/solar-equipment/inverters/canadian-solar-inc/canadian-solar-inc-csi-50ktl-gs-480v/)