title: "ABB: UNO-DM-33-TL-PLUS-US-SZM-RA Inverter (3,000W)"
url: https://epri-peac.com/solar-equipment/inverters/abb/abb-uno-dm-33-tl-plus-us-szm-ra-208v/
description: "CEC specs for ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V}: 3,000W AC, 208V, 20A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V} — CEC Inverter Specifications

Manufacturer: [**ABB**](https://epri-peac.com/solar-equipment/brands/abb/) Registry: **CEC Verified Engineering Specification**

ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V} outputs 3,000 W AC at 208 V, commercial single-phase (14.4 A continuous, 20 A OCPD), ranking #2,081 of 2,343 CEC inverters at 95.8% efficiency with a 200-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 3,000 W

- **AC Voltage** : 208 V, commercial single-phase

- **Min PV Breaker** : 20 A (12 AWG Cu)

- **CEC Efficiency** : 95.8%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V} Compare Against Peer CEC Listings?

NEC 705.12 breaker requirements, efficiency placement, and 208 V, commercial single-phase grid-support overview for ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V}. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.

Rated at 3,000 W AC (14.4 A continuous), ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V} ranks #2,081 of 2,343 CEC units at 95.8% efficiency (-0.61 pts vs the 96.41% 208 V median). Minimum 75 C copper conductor sizing for its 20 A circuit is 12 AWG Cu per NEC Table 310.16. Cold-weather string Voc must remain under 480 V DC at record local winter lows.

## Where Does ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V} Fall Across Listed CEC Models?

Marks ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V} (3,000 W AC) across the California Energy Commission inverter AC capacity distribution. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

## What Dataset Percentiles Define ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V}?

Benchmarks ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V} continuous AC output, 95.8% CEC weighted efficiency, and 20 A OCPD breaker demand. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

## What Do the Dataset Ranks Show for ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V}?

Four key NEC 705.12 and California Energy Commission metrics defining ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V} by ABB. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.

Eff #2,081 / 2,343

### 95.8% CEC Weighted Efficiency

-0.61 pts vs the 96.41% 208 V median; overall power rank #1,729 (3,000 W, below CEC median; higher than 25.3% of peers).

NEC 705.12 Check

### 20 A Required Backfeed OCPD

125% x 14.4 A = 18.0 A -> 20 A standard OCPD using 12 AWG Cu (75 C).

MPPT Window

### 200 V - 480 V (Max 480 V DC)

Tracking span of 280.0 V; listed since 2020-08-21 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### PASS (120% Commercial Busbar)

Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 3000.0W / 208 V -> 14.4 A | Breaker >= 1.25 * 14.4 = 18.0 A -> 20 A

CEC Inverters.csv for ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V}: Paco=3000.0 W, Vac=208 V, Vdcmax=480.0 V, Eff=95.8%.

**Result:** Min 20 A breaker & 12 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V}?

Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V}. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

Official California Energy Commission (NREL SAM) test parameters for ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 3,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 480 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 200 V - 480 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 9.21045 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 95.8% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2020-08-21 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V} (208 V, commercial single-phase)?

Evaluates ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V} (20 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.

Evaluates ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V} (20 A required OCPD at 208 V, commercial single-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (208V)** | 40 A | 20 A | PASS (120% Commercial Busbar) |
| **400A Bus / 400A Main (208V)** | 80 A | 20 A | PASS (120% Commercial Busbar) |
| **600A Bus / 600A Main (208V)** | 120 A | 20 A | PASS (120% Commercial Busbar) |
| **800A Bus / 800A Main (208V)** | 160 A | 20 A | PASS (120% Commercial Busbar) |
| **1,200A Bus / 1,200A Main (208V)** | 240 A | 20 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V}?

Sample PV string lengths aligned within 200-480 V MPPT and 480 V DC max at -10 C. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.

Sampled CEC PV modules aligned within 200.0-480.0 V MPPT and 480.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 5 to 8 panels | 4.72 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 6 to 11 panels | 4.84 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 6 to 10 panels | 4.25 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 7 to 11 panels | 2.2 kW |

## Which Competing Grid-Support Inverters Compare to ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V}?

Competing CEC grid-support inverters near 3,000 W AC and 208 V, commercial single-phase, led by Delta Electronics: SOLIVIA 38 NA G4 TL {208V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Delta Electronics: SOLIVIA 38 NA G4 TL {208V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-solivia-38-na-g4-tl-208v/) Delta Electronics | 3,320 W | +320 W | 208.0 V | 500.0 V | 97.23% |
| [**Delta Electronics: M4-TL-US {208V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-m4-tl-us-208v/) Delta Electronics | 3,330 W | +330 W | 208.0 V | 480.0 V | 97.27% |
| [**Delta Electronics: E4_BDI {208V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-e4-bdi-208v/) Delta Electronics | 3,341 W | +341 W | 208.0 V | 480.0 V | 97.43% |
| [**Delta Electronics: E4-TL-US {208V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-e4-tl-us-208v/) Delta Electronics | 3,360 W | +360 W | 208.0 V | 480.0 V | 97.64% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V}?

Check ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V} (3,000 W AC, 20 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V}.

### ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V} Panel & Wire Spec

Size 75 C copper conductors at 12 AWG Cu on a 20 A OCPD breaker (14.4 A continuous).

### Alternative Inverter Comparison

Compare efficiency (95.8%) and MPPT window (200-480 V) directly against Delta Electronics: SOLIVIA 38 NA G4 TL {208V} (3,320 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V} by ABB covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.

### What breaker and wire size does ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V} require?

At 3,000 W continuous AC (208 V, commercial single-phase), continuous current is 14.4 A; 125% NEC 690.8/705.12 sizing requires a 20 A breaker and 12 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V} require?

At 3,000 W AC and 208 V, commercial single-phase, continuous line current is 14.4 A, requiring a 20 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.

### How does ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V} compare to Delta Electronics: SOLIVIA 38 NA G4 TL {208V}?

ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V} delivers 3,000 W AC at 95.8% CEC efficiency with a 480 V DC ceiling, while Delta Electronics: SOLIVIA 38 NA G4 TL {208V} outputs 3,320 W at 208 V, commercial single-phase.

## Related Pages

Explore ABB hardware, Delta Electronics: SOLIVIA 38 NA G4 TL {208V}, utility rates, and NEC 705.12 sizing calculators alongside ABB: UNO-DM-33-TL-PLUS-US-SZM-RA {208V}.

[All ABB Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/abb/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From ABB

- [All ABB Specs](https://epri-peac.com/solar-equipment/brands/abb/)
- [ABB: PVS-175-TL-POWER-MODULE-1-US {800V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-175-tl-power-module-1-us-800v/)
- [ABB: PVS-175-TL-POWER-MODULE-2-US {800V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-175-tl-power-module-2-us-800v/)
- [ABB: PVS-166-TL-POWER-MODULE-1-US {800V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-166-tl-power-module-1-us-800v/)
- [ABB: PVS-166-TL-POWER-MODULE-2-US {800V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-166-tl-power-module-2-us-800v/)
- [ABB: PVS-60-TL-R-US {480V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-60-tl-r-us-480v/)