title: "ABB: PVS-60-TL-S-US {480V} Inverter (60,033W)"
url: https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-60-tl-s-us-480v/
description: "CEC specs for ABB: PVS-60-TL-S-US {480V}: 60,033W AC, 480V, 100A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# ABB: PVS-60-TL-S-US {480V} — CEC Inverter Specifications

Manufacturer: [**ABB**](https://epri-peac.com/solar-equipment/brands/abb/) Registry: **CEC Verified Engineering Specification**

ABB: PVS-60-TL-S-US {480V} outputs 60,033 W AC at 480 V, 3-phase (72.2 A continuous, 100 A OCPD), ranking #255 of 2,343 CEC inverters at 98.18% efficiency with a 570-800 V MPPT window and 800 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 60,033 W

- **AC Voltage** : 480 V, 3-phase

- **Min PV Breaker** : 100 A (3 AWG Cu)

- **CEC Efficiency** : 98.18%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does ABB: PVS-60-TL-S-US {480V} Compare Against Peer CEC Listings?

CEC efficiency rank (#255), 570-800 V MPPT tracking, and panel fit for ABB: PVS-60-TL-S-US {480V}. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.

ABB: PVS-60-TL-S-US {480V} from ABB outputs 72.2 A continuous AC at 480 V, 3-phase (60,033 W AC, rank #401). Paired with 3 AWG Cu conductors and a 100 A OCPD, its 98.18% CEC efficiency compares closely with Delta Electronics: M60U_280 {480V} (60,019 W). Keep NEC 690.7 winter string Voc below 800 V DC.

## Where Does ABB: PVS-60-TL-S-US {480V} Fall Across Listed CEC Models?

CEC inverter wattage histogram highlighting ABB: PVS-60-TL-S-US {480V} at 60,033 W continuous AC output. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

## What Dataset Percentiles Define ABB: PVS-60-TL-S-US {480V}?

Dataset percentiles comparing ABB: PVS-60-TL-S-US {480V} against 2,343 certified grid-support inverters nationwide. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.

## What Do the Dataset Ranks Show for ABB: PVS-60-TL-S-US {480V}?

Engineering highlights for ABB: PVS-60-TL-S-US {480V} covering efficiency, 3 AWG Cu feeder, and panel compatibility. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.

Eff #255 / 2,343

### 98.18% CEC Weighted Efficiency

+0.16 pts vs the 98.02% 480 V median; overall power rank #401 (60,033 W, top 17.3%; higher than 82.7% of peers).

NEC 705.12 Check

### 100 A Required Backfeed OCPD

125% x 72.2 A = 90.2 A -> 100 A standard OCPD using 3 AWG Cu (75 C).

MPPT Window

### 570 V - 800 V (Max 800 V DC)

Tracking span of 230.0 V; listed since 2020-09-01 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 60033.0W / 480 V 3-phase -> 72.2 A | Breaker >= 1.25 * 72.2 = 90.2 A -> 100 A

CEC Inverters.csv for ABB: PVS-60-TL-S-US {480V}: Paco=60033.0 W, Vac=480 V, Vdcmax=800.0 V, Eff=98.18%.

**Result:** Min 100 A breaker & 3 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for ABB: PVS-60-TL-S-US {480V}?

California Energy Commission Solar Equipment List parameters for ABB: PVS-60-TL-S-US {480V} (grid-tied PV inverter) interconnection. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Official California Energy Commission (NREL SAM) test parameters for ABB: PVS-60-TL-S-US {480V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 60,033 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 800 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 570 V - 800 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 84.9267 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 98.18% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2020-09-01 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to ABB: PVS-60-TL-S-US {480V} (480 V, 3-phase)?

Panelboard and switchgear backfeed allowances for ABB: PVS-60-TL-S-US {480V} (100 A OCPD). Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.

Evaluates ABB: PVS-60-TL-S-US {480V} (100 A required OCPD at 480 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (480V)** | 40 A | 100 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (480V)** | 80 A | 100 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (480V)** | 120 A | 100 A | PASS (120% Commercial Busbar) |
| **800A Bus / 800A Main (480V)** | 160 A | 100 A | PASS (120% Commercial Busbar) |
| **1,200A Bus / 1,200A Main (480V)** | 240 A | 100 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With ABB: PVS-60-TL-S-US {480V}?

Representative PV panel pairings verified under NEC 690.7 cold Voc for ABB: PVS-60-TL-S-US {480V}. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.

Sampled CEC PV modules aligned within 570.0-800.0 V MPPT and 800.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 14 panels (fixed) | 8.26 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 18 panels (fixed) | 7.92 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 17 panels (fixed) | 7.22 kW |
| [**Chint New Energy Technology Co Ltd CHSM72M(DG)/F-BH-515**](https://epri-peac.com/solar-equipment/modules/chint-new-energy-technology-co-ltd/chint-new-energy-technology-co-ltd-chsm72m-dg-f-bh-515/) | 515.0 W | 53.76 V | 14 panels (fixed) | 7.21 kW |

## Which Competing Grid-Support Inverters Compare to ABB: PVS-60-TL-S-US {480V}?

Four alternative CEC inverters matched to ABB: PVS-60-TL-S-US {480V} (60,033 W AC), led by Delta Electronics: M60U_280 {480V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Delta Electronics: M60U_280 {480V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-m60u-280-480v/) Delta Electronics | 60,019 W | -14 W | 480.0 V | 840.0 V | 98.51% |
| [**Canadian Solar Inc: CSI-60KTL-CT {480V}**](https://epri-peac.com/solar-equipment/inverters/canadian-solar-inc/canadian-solar-inc-csi-60ktl-ct-480v/) Canadian Solar Inc | 60,000 W | -33 W | 480.0 V | 850.0 V | 98.24% |
| [**Canadian Solar Inc: CSI-60KTL-GS {480V}**](https://epri-peac.com/solar-equipment/inverters/canadian-solar-inc/canadian-solar-inc-csi-60ktl-gs-480v/) Canadian Solar Inc | 60,000 W | -33 W | 480.0 V | 720.0 V | 98.34% |
| [**Chint Power Systems America: CPS SCA60KTL-DO/US-480 {480V}**](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-sca60ktl-do-us-480-480v/) Chint Power Systems America | 60,000 W | -33 W | 480.0 V | 850.0 V | 98.25% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for ABB: PVS-60-TL-S-US {480V}?

Check ABB: PVS-60-TL-S-US {480V} (60,033 W AC, 100 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 800 V DC on ABB: PVS-60-TL-S-US {480V}.

### ABB: PVS-60-TL-S-US {480V} Panel & Wire Spec

Size 75 C copper conductors at 3 AWG Cu on a 100 A OCPD breaker (72.2 A continuous).

### Alternative Inverter Comparison

Compare efficiency (98.18%) and MPPT window (570-800 V) directly against Delta Electronics: M60U_280 {480V} (60,019 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for ABB: PVS-60-TL-S-US {480V} by ABB covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.

### What breaker and wire size does ABB: PVS-60-TL-S-US {480V} require?

At 60,033 W continuous AC (480 V, 3-phase), continuous current is 72.2 A; 125% NEC 690.8/705.12 sizing requires a 100 A breaker and 3 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does ABB: PVS-60-TL-S-US {480V} require?

At 60,033 W AC and 480 V, 3-phase, continuous line current is 72.2 A, requiring a 100 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

### How does ABB: PVS-60-TL-S-US {480V} compare to Delta Electronics: M60U_280 {480V}?

ABB: PVS-60-TL-S-US {480V} delivers 60,033 W AC at 98.18% CEC efficiency with a 800 V DC ceiling, while Delta Electronics: M60U_280 {480V} outputs 60,019 W at 480 V, 3-phase.

## Related Pages

Explore ABB hardware, Delta Electronics: M60U_280 {480V}, utility rates, and NEC 705.12 sizing calculators alongside ABB: PVS-60-TL-S-US {480V}.

[All ABB Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/abb/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From ABB

- [All ABB Specs](https://epri-peac.com/solar-equipment/brands/abb/)
- [ABB: PVS-175-TL-POWER-MODULE-1-US {800V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-175-tl-power-module-1-us-800v/)
- [ABB: PVS-175-TL-POWER-MODULE-2-US {800V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-175-tl-power-module-2-us-800v/)
- [ABB: PVS-166-TL-POWER-MODULE-1-US {800V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-166-tl-power-module-1-us-800v/)
- [ABB: PVS-166-TL-POWER-MODULE-2-US {800V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-166-tl-power-module-2-us-800v/)
- [ABB: PVS-60-TL-R-US {480V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-60-tl-r-us-480v/)