title: "ABB: PVS-166-TL-POWER-MODULE-2-US Inverter (165,954W)"
url: https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-166-tl-power-module-2-us-800v/
description: "CEC specs for ABB: PVS-166-TL-POWER-MODULE-2-US {800V}: 165,954W AC, 800V, 150A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# ABB: PVS-166-TL-POWER-MODULE-2-US {800V} — CEC Inverter Specifications

Manufacturer: [**ABB**](https://epri-peac.com/solar-equipment/brands/abb/) Registry: **CEC Verified Engineering Specification**

ABB: PVS-166-TL-POWER-MODULE-2-US {800V} outputs 165,954 W AC at 800 V, 3-phase (119.8 A continuous, 150 A OCPD), ranking #210 of 2,343 CEC inverters at 98.26% efficiency with a 850-1,200 V MPPT window and 1,200 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 165,954 W

- **AC Voltage** : 800 V, 3-phase

- **Min PV Breaker** : 150 A (1/0 AWG Cu)

- **CEC Efficiency** : 98.26%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does ABB: PVS-166-TL-POWER-MODULE-2-US {800V} Compare Against Peer CEC Listings?

Breaker sizing (150 A), 1/0 AWG Cu wire rules, and DC input limits for ABB: PVS-166-TL-POWER-MODULE-2-US {800V}.

Classified as a grid-tied PV inverter (listed since 2020-09-01), ABB: PVS-166-TL-POWER-MODULE-2-US {800V} requires 149.8 A design capacity -> 150 A breaker using 1/0 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 98.26% (+1.44 pts vs overall CEC median) across 2,343 CEC models, while commercial 800 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (800v) or nec 705.11 supply-side tap.

## Where Does ABB: PVS-166-TL-POWER-MODULE-2-US {800V} Fall Across Listed CEC Models?

Output power comparison showing where ABB: PVS-166-TL-POWER-MODULE-2-US {800V} sits among all 2,343 CEC-listed grid-support inverters. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.

## What Dataset Percentiles Define ABB: PVS-166-TL-POWER-MODULE-2-US {800V}?

Relative ranking of ABB: PVS-166-TL-POWER-MODULE-2-US {800V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.

## What Do the Dataset Ranks Show for ABB: PVS-166-TL-POWER-MODULE-2-US {800V}?

Snapshot of ABB: PVS-166-TL-POWER-MODULE-2-US {800V} efficiency rank (#210), OCPD breaker size, MPPT span, and busbar verdict. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

Eff #210 / 2,343

### 98.26% CEC Weighted Efficiency

-0.04 pts vs the 98.3% 800 V median; overall power rank #265 (165,954 W, top 11.4%; higher than 88.6% of peers).

NEC 705.12 Check

### 150 A Required Backfeed OCPD

125% x 119.8 A = 149.8 A -> 150 A standard OCPD using 1/0 AWG Cu (75 C).

MPPT Window

### 850 V - 1,200 V (Max 1,200 V DC)

Tracking span of 350.0 V; listed since 2020-09-01 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 800 V, 3-phase switchgear (200A Bus / 200A Main (800V) to 1,200A Bus / 1,200A Main (800V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 165954.0W / 800 V 3-phase -> 119.8 A | Breaker >= 1.25 * 119.8 = 149.8 A -> 150 A

CEC Inverters.csv for ABB: PVS-166-TL-POWER-MODULE-2-US {800V}: Paco=165954.0 W, Vac=800 V, Vdcmax=1200.0 V, Eff=98.26%.

**Result:** Min 150 A breaker & 1/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (800V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for ABB: PVS-166-TL-POWER-MODULE-2-US {800V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for ABB: PVS-166-TL-POWER-MODULE-2-US {800V}. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.

Official California Energy Commission (NREL SAM) test parameters for ABB: PVS-166-TL-POWER-MODULE-2-US {800V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 165,954 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 800 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 1,200 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 850 V - 1,200 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 153.534 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 98.26% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2020-09-01 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to ABB: PVS-166-TL-POWER-MODULE-2-US {800V} (800 V, 3-phase)?

NEC 705.12(B)(3)(2) backfeed compliance table for ABB: PVS-166-TL-POWER-MODULE-2-US {800V} at 800 V, 3-phase. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Evaluates ABB: PVS-166-TL-POWER-MODULE-2-US {800V} (150 A required OCPD at 800 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (800V)** | 40 A | 150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (800V)** | 80 A | 150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (800V)** | 120 A | 150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (800V)** | 160 A | 150 A | PASS (120% Commercial Busbar) |
| **1,200A Bus / 1,200A Main (800V)** | 240 A | 150 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With ABB: PVS-166-TL-POWER-MODULE-2-US {800V}?

Minimum and maximum series solar module strings fitting ABB: PVS-166-TL-POWER-MODULE-2-US {800V} MPPT and 1,200 V limits. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.

Sampled CEC PV modules aligned within 850.0-1200.0 V MPPT and 1200.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 20 to 21 panels | 12.39 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 26 to 28 panels | 12.32 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 25 to 26 panels | 11.05 kW |
| [**Chint New Energy Technology Co Ltd CHSM72M(DG)/F-BH-515**](https://epri-peac.com/solar-equipment/modules/chint-new-energy-technology-co-ltd/chint-new-energy-technology-co-ltd-chsm72m-dg-f-bh-515/) | 515.0 W | 53.76 V | 21 to 22 panels | 11.33 kW |

## Which Competing Grid-Support Inverters Compare to ABB: PVS-166-TL-POWER-MODULE-2-US {800V}?

Peer 800 V, 3-phase CEC inverters near 165,954 W AC output such as Chint Power Systems America: CPS ECB200KTL/US-800 {800V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Chint Power Systems America: CPS ECB200KTL/US-800 {800V}**](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-ecb200ktl-us-800-800v/) Chint Power Systems America | 200,000 W | +34046 W | 800.0 V | 1500.0 V | 97.55% |
| [**Sungrow Power Supply Co Ltd: SG250HX-US {800V}**](https://epri-peac.com/solar-equipment/inverters/sungrow-power-supply-co-ltd/sungrow-power-supply-co-ltd-sg250hx-us-800v/) Sungrow Power Supply Co Ltd | 226,997 W | +61043 W | 800.0 V | 1300.0 V | 98.52% |
| [**Huawei Technologies Co Ltd: SUN2000-100KTL-USH0 {800V}**](https://epri-peac.com/solar-equipment/inverters/huawei-technologies-co-ltd/huawei-technologies-co-ltd-sun2000-100ktl-ush0-800v/) Huawei Technologies Co Ltd | 100,000 W | -65954 W | 800.0 V | 1200.0 V | 98.57% |
| [**Ginlong Technologies Co Ltd: Solis-255K-EHV-5G-US-PLUS {800V}**](https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-solis-255k-ehv-5g-us-plus-800v/) Ginlong Technologies Co Ltd | 238,706 W | +72752 W | 800.0 V | 1300.0 V | 98.26% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for ABB: PVS-166-TL-POWER-MODULE-2-US {800V}?

Check ABB: PVS-166-TL-POWER-MODULE-2-US {800V} (165,954 W AC, 150 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 800 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (800V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,200 V DC on ABB: PVS-166-TL-POWER-MODULE-2-US {800V}.

### ABB: PVS-166-TL-POWER-MODULE-2-US {800V} Panel & Wire Spec

Size 75 C copper conductors at 1/0 AWG Cu on a 150 A OCPD breaker (119.8 A continuous).

### Alternative Inverter Comparison

Compare efficiency (98.26%) and MPPT window (850-1,200 V) directly against Chint Power Systems America: CPS ECB200KTL/US-800 {800V} (200,000 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for ABB: PVS-166-TL-POWER-MODULE-2-US {800V} by ABB covering breaker sizing, MPPT limits, and 800 V, 3-phase interconnection. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

### What breaker and wire size does ABB: PVS-166-TL-POWER-MODULE-2-US {800V} require?

At 165,954 W continuous AC (800 V, 3-phase), continuous current is 119.8 A; 125% NEC 690.8/705.12 sizing requires a 150 A breaker and 1/0 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does ABB: PVS-166-TL-POWER-MODULE-2-US {800V} require?

At 165,954 W AC and 800 V, 3-phase, continuous line current is 119.8 A, requiring a 150 A OCPD and 1,200A Bus / 1,200A Main (800V) or NEC 705.11 interconnection.

### How does ABB: PVS-166-TL-POWER-MODULE-2-US {800V} compare to Chint Power Systems America: CPS ECB200KTL/US-800 {800V}?

ABB: PVS-166-TL-POWER-MODULE-2-US {800V} delivers 165,954 W AC at 98.26% CEC efficiency with a 1,200 V DC ceiling, while Chint Power Systems America: CPS ECB200KTL/US-800 {800V} outputs 200,000 W at 800 V, 3-phase.

## Related Pages

Explore ABB hardware, Chint Power Systems America: CPS ECB200KTL/US-800 {800V}, utility rates, and NEC 705.12 sizing calculators alongside ABB: PVS-166-TL-POWER-MODULE-2-US {800V}.

[All ABB Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/abb/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From ABB

- [All ABB Specs](https://epri-peac.com/solar-equipment/brands/abb/)
- [ABB: PVS-175-TL-POWER-MODULE-1-US {800V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-175-tl-power-module-1-us-800v/)
- [ABB: PVS-175-TL-POWER-MODULE-2-US {800V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-175-tl-power-module-2-us-800v/)
- [ABB: PVS-166-TL-POWER-MODULE-1-US {800V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-166-tl-power-module-1-us-800v/)
- [ABB: PVS-60-TL-R-US {480V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-60-tl-r-us-480v/)
- [ABB: PVS-60-TL-S-R-US {480V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-60-tl-s-r-us-480v/)