title: "ABB: PVI-42-OUTD-S-US-Z-M-A {277V} Inverter (4,200W)"
url: https://epri-peac.com/solar-equipment/inverters/abb/abb-pvi-42-outd-s-us-z-m-a-277v/
description: "CEC specs for ABB: PVI-42-OUTD-S-US-Z-M-A {277V}: 4,200W AC, 277V, 15A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# ABB: PVI-42-OUTD-S-US-Z-M-A {277V} — CEC Inverter Specifications

Manufacturer: [**ABB**](https://epri-peac.com/solar-equipment/brands/abb/) Registry: **CEC Verified Engineering Specification**

ABB: PVI-42-OUTD-S-US-Z-M-A {277V} outputs 4,200 W AC at 480Y/277 V, 3-phase (5.1 A continuous, 15 A OCPD), ranking #1,333 of 2,343 CEC inverters at 96.62% efficiency with a 100-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 4,200 W

- **AC Voltage** : 480Y/277 V, 3-phase

- **Min PV Breaker** : 15 A (14 AWG Cu)

- **CEC Efficiency** : 96.62%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does ABB: PVI-42-OUTD-S-US-Z-M-A {277V} Compare Against Peer CEC Listings?

NEC 705.12 breaker requirements, efficiency placement, and 480Y/277 V, 3-phase grid-support overview for ABB: PVI-42-OUTD-S-US-Z-M-A {277V}. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.

Rated at 4,200 W AC (5.1 A continuous), ABB: PVI-42-OUTD-S-US-Z-M-A {277V} ranks #1,333 of 2,343 CEC units at 96.62% efficiency (-0.20 pts vs the 96.82% 277 V median). Minimum 75 C copper conductor sizing for its 15 A circuit is 14 AWG Cu per NEC Table 310.16. Cold-weather string Voc must remain under 480 V DC at record local winter lows.

## Where Does ABB: PVI-42-OUTD-S-US-Z-M-A {277V} Fall Across Listed CEC Models?

Marks ABB: PVI-42-OUTD-S-US-Z-M-A {277V} (4,200 W AC) across the California Energy Commission inverter AC capacity distribution. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.

## What Dataset Percentiles Define ABB: PVI-42-OUTD-S-US-Z-M-A {277V}?

Benchmarks ABB: PVI-42-OUTD-S-US-Z-M-A {277V} continuous AC output, 96.62% CEC weighted efficiency, and 15 A OCPD breaker demand. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.

## What Do the Dataset Ranks Show for ABB: PVI-42-OUTD-S-US-Z-M-A {277V}?

Four key NEC 705.12 and California Energy Commission metrics defining ABB: PVI-42-OUTD-S-US-Z-M-A {277V} by ABB. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

Eff #1,333 / 2,343

### 96.62% CEC Weighted Efficiency

-0.20 pts vs the 96.82% 277 V median; overall power rank #1,605 (4,200 W, below CEC median; higher than 30.9% of peers).

NEC 705.12 Check

### 15 A Required Backfeed OCPD

125% x 5.1 A = 6.4 A -> 15 A standard OCPD using 14 AWG Cu (75 C).

MPPT Window

### 100 V - 480 V (Max 480 V DC)

Tracking span of 380.0 V; listed since 2018-10-15 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### PASS (120% Commercial Busbar)

Evaluated for 480Y/277 V, 3-phase switchgear (200A Bus / 200A Main (277V) to 1,200A Bus / 1,200A Main (277V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 4200.0W / 480 V 3-phase -> 5.1 A | Breaker >= 1.25 * 5.1 = 6.4 A -> 15 A

CEC Inverters.csv for ABB: PVI-42-OUTD-S-US-Z-M-A {277V}: Paco=4200.0 W, Vac=277 V, Vdcmax=480.0 V, Eff=96.62%.

**Result:** Min 15 A breaker & 14 AWG Cu (75 C); 1,200A Bus / 1,200A Main (277V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for ABB: PVI-42-OUTD-S-US-Z-M-A {277V}?

Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for ABB: PVI-42-OUTD-S-US-Z-M-A {277V}. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.

Official California Energy Commission (NREL SAM) test parameters for ABB: PVI-42-OUTD-S-US-Z-M-A {277V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 4,200 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 480Y/277 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 480 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 100 V - 480 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 11.0054 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 96.62% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2018-10-15 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to ABB: PVI-42-OUTD-S-US-Z-M-A {277V} (480Y/277 V, 3-phase)?

Evaluates ABB: PVI-42-OUTD-S-US-Z-M-A {277V} (15 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.

Evaluates ABB: PVI-42-OUTD-S-US-Z-M-A {277V} (15 A required OCPD at 480Y/277 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (277V)** | 40 A | 15 A | PASS (120% Commercial Busbar) |
| **400A Bus / 400A Main (277V)** | 80 A | 15 A | PASS (120% Commercial Busbar) |
| **600A Bus / 600A Main (277V)** | 120 A | 15 A | PASS (120% Commercial Busbar) |
| **800A Bus / 800A Main (277V)** | 160 A | 15 A | PASS (120% Commercial Busbar) |
| **1,200A Bus / 1,200A Main (277V)** | 240 A | 15 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With ABB: PVI-42-OUTD-S-US-Z-M-A {277V}?

Sample PV string lengths aligned within 100-480 V MPPT and 480 V DC max at -10 C. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

Sampled CEC PV modules aligned within 100.0-480.0 V MPPT and 480.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 3 to 8 panels | 4.72 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 3 to 11 panels | 4.84 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 3 to 10 panels | 4.25 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 4 to 11 panels | 2.2 kW |

## Which Competing Grid-Support Inverters Compare to ABB: PVI-42-OUTD-S-US-Z-M-A {277V}?

Competing CEC grid-support inverters near 4,200 W AC and 480Y/277 V, 3-phase, led by Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {277V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {277V}**](https://epri-peac.com/solar-equipment/inverters/shenzhen-growatt-new-energy-co-ltd/shenzhen-growatt-new-energy-co-ltd-growatt-4000mtlp-us-277v/) Shenzhen Growatt New Energy Co Ltd | 4,060 W | -140 W | 277.0 V | 550.0 V | 97.23% |
| [**Shenzhen Growatt New Energy Co Ltd: GROWATT 5000MTLP-US {277V}**](https://epri-peac.com/solar-equipment/inverters/shenzhen-growatt-new-energy-co-ltd/shenzhen-growatt-new-energy-co-ltd-growatt-5000mtlp-us-277v/) Shenzhen Growatt New Energy Co Ltd | 5,060 W | +860 W | 277.0 V | 550.0 V | 97.1% |
| [**Shenzhen Growatt New Energy Co Ltd: GROWATT 6000MTLP-US {277V}**](https://epri-peac.com/solar-equipment/inverters/shenzhen-growatt-new-energy-co-ltd/shenzhen-growatt-new-energy-co-ltd-growatt-6000mtlp-us-277v/) Shenzhen Growatt New Energy Co Ltd | 6,080 W | +1880 W | 277.0 V | 550.0 V | 97.0% |
| [**Shenzhen Growatt New Energy Co Ltd: GROWATT 7000MTLP-US {277V}**](https://epri-peac.com/solar-equipment/inverters/shenzhen-growatt-new-energy-co-ltd/shenzhen-growatt-new-energy-co-ltd-growatt-7000mtlp-us-277v/) Shenzhen Growatt New Energy Co Ltd | 7,016 W | +2816 W | 277.0 V | 480.0 V | 96.5% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for ABB: PVI-42-OUTD-S-US-Z-M-A {277V}?

Check ABB: PVI-42-OUTD-S-US-Z-M-A {277V} (4,200 W AC, 15 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480Y/277 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (277V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on ABB: PVI-42-OUTD-S-US-Z-M-A {277V}.

### ABB: PVI-42-OUTD-S-US-Z-M-A {277V} Panel & Wire Spec

Size 75 C copper conductors at 14 AWG Cu on a 15 A OCPD breaker (5.1 A continuous).

### Alternative Inverter Comparison

Compare efficiency (96.62%) and MPPT window (100-480 V) directly against Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {277V} (4,060 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for ABB: PVI-42-OUTD-S-US-Z-M-A {277V} by ABB covering breaker sizing, MPPT limits, and 480Y/277 V, 3-phase interconnection.

### What breaker and wire size does ABB: PVI-42-OUTD-S-US-Z-M-A {277V} require?

At 4,200 W continuous AC (480Y/277 V, 3-phase), continuous current is 5.1 A; 125% NEC 690.8/705.12 sizing requires a 15 A breaker and 14 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does ABB: PVI-42-OUTD-S-US-Z-M-A {277V} require?

At 4,200 W AC and 480Y/277 V, 3-phase, continuous line current is 5.1 A, requiring a 15 A OCPD and 1,200A Bus / 1,200A Main (277V) or NEC 705.11 interconnection.

### How does ABB: PVI-42-OUTD-S-US-Z-M-A {277V} compare to Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {277V}?

ABB: PVI-42-OUTD-S-US-Z-M-A {277V} delivers 4,200 W AC at 96.62% CEC efficiency with a 480 V DC ceiling, while Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {277V} outputs 4,060 W at 480Y/277 V, 3-phase.

## Related Pages

Explore ABB hardware, Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {277V}, utility rates, and NEC 705.12 sizing calculators alongside ABB: PVI-42-OUTD-S-US-Z-M-A {277V}.

[All ABB Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/abb/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From ABB

- [All ABB Specs](https://epri-peac.com/solar-equipment/brands/abb/)
- [ABB: PVS-175-TL-POWER-MODULE-1-US {800V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-175-tl-power-module-1-us-800v/)
- [ABB: PVS-175-TL-POWER-MODULE-2-US {800V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-175-tl-power-module-2-us-800v/)
- [ABB: PVS-166-TL-POWER-MODULE-1-US {800V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-166-tl-power-module-1-us-800v/)
- [ABB: PVS-166-TL-POWER-MODULE-2-US {800V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-166-tl-power-module-2-us-800v/)
- [ABB: PVS-60-TL-R-US {480V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-60-tl-r-us-480v/)