title: "ABB: PVI-38-OUTD-S-US-Z-M-A {208V} Inverter (3,800W)"
url: https://epri-peac.com/solar-equipment/inverters/abb/abb-pvi-38-outd-s-us-z-m-a-208v/
description: "CEC specs for ABB: PVI-38-OUTD-S-US-Z-M-A {208V}: 3,800W AC, 208V, 25A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# ABB: PVI-38-OUTD-S-US-Z-M-A {208V} — CEC Inverter Specifications

Manufacturer: [**ABB**](https://epri-peac.com/solar-equipment/brands/abb/) Registry: **CEC Verified Engineering Specification**

ABB: PVI-38-OUTD-S-US-Z-M-A {208V} outputs 3,800 W AC at 208 V, commercial single-phase (18.3 A continuous, 25 A OCPD), ranking #2,128 of 2,343 CEC inverters at 95.65% efficiency with a 100-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 3,800 W

- **AC Voltage** : 208 V, commercial single-phase

- **Min PV Breaker** : 25 A (10 AWG Cu)

- **CEC Efficiency** : 95.65%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does ABB: PVI-38-OUTD-S-US-Z-M-A {208V} Compare Against Peer CEC Listings?

CEC efficiency rank (#2,128), 100-480 V MPPT tracking, and panel fit for ABB: PVI-38-OUTD-S-US-Z-M-A {208V}. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.

Operating at 208 V, commercial single-phase, ABB: PVI-38-OUTD-S-US-Z-M-A {208V} converts DC array energy at 95.65% CEC weighted efficiency (below overall CEC median; higher than 9.1% of peers) with a 480 V max DC input and 12.8156 A max input current for NEC 690.7 string safety. Compare this 3,800 W grid-tied PV inverter directly with Delta Electronics: M5-TL-US {208V} (4,160 W). Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.

## Where Does ABB: PVI-38-OUTD-S-US-Z-M-A {208V} Fall Across Listed CEC Models?

CEC inverter wattage histogram highlighting ABB: PVI-38-OUTD-S-US-Z-M-A {208V} at 3,800 W continuous AC output. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.

## What Dataset Percentiles Define ABB: PVI-38-OUTD-S-US-Z-M-A {208V}?

Dataset percentiles comparing ABB: PVI-38-OUTD-S-US-Z-M-A {208V} against 2,343 certified grid-support inverters nationwide. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.

## What Do the Dataset Ranks Show for ABB: PVI-38-OUTD-S-US-Z-M-A {208V}?

Engineering highlights for ABB: PVI-38-OUTD-S-US-Z-M-A {208V} covering efficiency, 10 AWG Cu feeder, and panel compatibility. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Eff #2,128 / 2,343

### 95.65% CEC Weighted Efficiency

-0.76 pts vs the 96.41% 208 V median; overall power rank #1,650 (3,800 W, below CEC median; higher than 28.7% of peers).

NEC 705.12 Check

### 25 A Required Backfeed OCPD

125% x 18.3 A = 22.9 A -> 25 A standard OCPD using 10 AWG Cu (75 C).

MPPT Window

### 100 V - 480 V (Max 480 V DC)

Tracking span of 380.0 V; listed since 2018-10-15 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### PASS (120% Commercial Busbar)

Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 3800.0W / 208 V -> 18.3 A | Breaker >= 1.25 * 18.3 = 22.9 A -> 25 A

CEC Inverters.csv for ABB: PVI-38-OUTD-S-US-Z-M-A {208V}: Paco=3800.0 W, Vac=208 V, Vdcmax=480.0 V, Eff=95.65%.

**Result:** Min 25 A breaker & 10 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for ABB: PVI-38-OUTD-S-US-Z-M-A {208V}?

California Energy Commission Solar Equipment List parameters for ABB: PVI-38-OUTD-S-US-Z-M-A {208V} (grid-tied PV inverter) interconnection. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

Official California Energy Commission (NREL SAM) test parameters for ABB: PVI-38-OUTD-S-US-Z-M-A {208V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 3,800 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 480 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 100 V - 480 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 12.8156 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 95.65% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2018-10-15 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to ABB: PVI-38-OUTD-S-US-Z-M-A {208V} (208 V, commercial single-phase)?

Panelboard and switchgear backfeed allowances for ABB: PVI-38-OUTD-S-US-Z-M-A {208V} (25 A OCPD). All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

Evaluates ABB: PVI-38-OUTD-S-US-Z-M-A {208V} (25 A required OCPD at 208 V, commercial single-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (208V)** | 40 A | 25 A | PASS (120% Commercial Busbar) |
| **400A Bus / 400A Main (208V)** | 80 A | 25 A | PASS (120% Commercial Busbar) |
| **600A Bus / 600A Main (208V)** | 120 A | 25 A | PASS (120% Commercial Busbar) |
| **800A Bus / 800A Main (208V)** | 160 A | 25 A | PASS (120% Commercial Busbar) |
| **1,200A Bus / 1,200A Main (208V)** | 240 A | 25 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With ABB: PVI-38-OUTD-S-US-Z-M-A {208V}?

Representative PV panel pairings verified under NEC 690.7 cold Voc for ABB: PVI-38-OUTD-S-US-Z-M-A {208V}. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.

Sampled CEC PV modules aligned within 100.0-480.0 V MPPT and 480.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 3 to 8 panels | 4.72 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 3 to 11 panels | 4.84 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 3 to 10 panels | 4.25 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 4 to 11 panels | 2.2 kW |

## Which Competing Grid-Support Inverters Compare to ABB: PVI-38-OUTD-S-US-Z-M-A {208V}?

Four alternative CEC inverters matched to ABB: PVI-38-OUTD-S-US-Z-M-A {208V} (3,800 W AC), led by Delta Electronics: M5-TL-US {208V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Delta Electronics: M5-TL-US {208V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-m5-tl-us-208v/) Delta Electronics | 4,160 W | +360 W | 208.0 V | 480.0 V | 97.35% |
| [**Delta Electronics: E4-TL-US(AC) {208V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-e4-tl-us-ac-208v/) Delta Electronics | 3,364 W | -436 W | 208.0 V | 480.0 V | 98.11% |
| [**Delta Electronics: E4-TL-US {208V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-e4-tl-us-208v/) Delta Electronics | 3,360 W | -440 W | 208.0 V | 480.0 V | 97.64% |
| [**Delta Electronics: E4_BDI {208V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-e4-bdi-208v/) Delta Electronics | 3,341 W | -459 W | 208.0 V | 480.0 V | 97.43% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for ABB: PVI-38-OUTD-S-US-Z-M-A {208V}?

Check ABB: PVI-38-OUTD-S-US-Z-M-A {208V} (3,800 W AC, 25 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on ABB: PVI-38-OUTD-S-US-Z-M-A {208V}.

### ABB: PVI-38-OUTD-S-US-Z-M-A {208V} Panel & Wire Spec

Size 75 C copper conductors at 10 AWG Cu on a 25 A OCPD breaker (18.3 A continuous).

### Alternative Inverter Comparison

Compare efficiency (95.65%) and MPPT window (100-480 V) directly against Delta Electronics: M5-TL-US {208V} (4,160 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for ABB: PVI-38-OUTD-S-US-Z-M-A {208V} by ABB covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.

### What breaker and wire size does ABB: PVI-38-OUTD-S-US-Z-M-A {208V} require?

At 3,800 W continuous AC (208 V, commercial single-phase), continuous current is 18.3 A; 125% NEC 690.8/705.12 sizing requires a 25 A breaker and 10 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does ABB: PVI-38-OUTD-S-US-Z-M-A {208V} require?

At 3,800 W AC and 208 V, commercial single-phase, continuous line current is 18.3 A, requiring a 25 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.

### How does ABB: PVI-38-OUTD-S-US-Z-M-A {208V} compare to Delta Electronics: M5-TL-US {208V}?

ABB: PVI-38-OUTD-S-US-Z-M-A {208V} delivers 3,800 W AC at 95.65% CEC efficiency with a 480 V DC ceiling, while Delta Electronics: M5-TL-US {208V} outputs 4,160 W at 208 V, commercial single-phase.

## Related Pages

Explore ABB hardware, Delta Electronics: M5-TL-US {208V}, utility rates, and NEC 705.12 sizing calculators alongside ABB: PVI-38-OUTD-S-US-Z-M-A {208V}.

[All ABB Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/abb/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From ABB

- [All ABB Specs](https://epri-peac.com/solar-equipment/brands/abb/)
- [ABB: PVS-175-TL-POWER-MODULE-1-US {800V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-175-tl-power-module-1-us-800v/)
- [ABB: PVS-175-TL-POWER-MODULE-2-US {800V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-175-tl-power-module-2-us-800v/)
- [ABB: PVS-166-TL-POWER-MODULE-1-US {800V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-166-tl-power-module-1-us-800v/)
- [ABB: PVS-166-TL-POWER-MODULE-2-US {800V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-166-tl-power-module-2-us-800v/)
- [ABB: PVS-60-TL-R-US {480V}](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-60-tl-r-us-480v/)